background image

www.desatech.com

113896-01D

1

INSPECTING BURNERS

Continued

BURNER INjECTOR HOLDER AND 
PILOT AIR INLET HOLE

The  primary  air  inlet  holes  allow  the  proper 

amount of air to mix with the gas. This provides 

a clean burning flame. Keep these holes clear of 

dust, dirt, lint and pet hair. Clean these air inlet 

holes prior to each heating season. Blocked air 

holes will create soot. We recommend that you 

clean the unit every three months during operation 

and have heater inspected yearly by a qualified 

service person.

We also recommend that you keep the burner 

tube and pilot assembly clean and free of dust and 

dirt. To clean these parts we recommend using 

compressed air no greater than 30 PSI. Your local 

computer store, hardware store or home center 

may carry compressed air in a can. You can use a 

vacuum cleaner in the blow position. If using com

-

pressed air in a can, please follow the directions on 

the can. If you don’t follow directions on the can, 

you could damage the pilot assembly.

1.  Shut off the unit, including the pilot. Allow 

the unit to cool for at least thirty minutes.

2.  Inspect burner, pilot and primary air inlet 

holes on injector holder for dust and dirt (see 

Figure 34).

3.  Blow air through the ports/slots and holes in 

the burner.

4.  Check the injector holder located at the end 

of the burner tube again. Remove any large 

particles of dust, dirt, lint or pet hair with a 

soft cloth or vacuum cleaner nozzle.

5.  Blow air into the primary air holes on the 

injector holder.

6.  In case any large clumps of dust have now been 

pushed into the burner repeat steps 3 and 4.

BURNER PRIMARY AIR HOLES

Air is drawn into the burner through the holes in 

the fitting at the burner entrance. These holes may 

become blocked with dust or lint. Periodically 

inspect these holes for any blockage and clean if 

needed. Blocked air holes will create soot.

MAIN BURNER

Periodically inspect all burner flame holes with the 

heater running. All slotted burner flame holes should 

be open with yellow flame present. All round burner 

flame holes should be open with a small blue flame 

present. Some burner flame holes may become 

blocked by debris or rust, with no flame present. If 

so, turn off heater and let cool. Remove blockage. 

Blocked burner flame holes will create soot. 

CLEANING AND 

MAINTENANCE

  WARNING:  Turn  off  heater 

and let cool before cleaning.

  CAUTION:  You  must  keep 

control areas, burner and circu-

lating air passageways of heater 

clean.  Inspect  these  areas  of 

heater  before  each  use.  Have 

heater  inspected  yearly  by  a 

qualified service person. Heater 

may need more frequent clean-

ing  due  to  excessive  lint  from 

carpeting, bedding material, pet 

hair, etc.

  WARNING:  Failure  to  keep 

the  primary  air  opening(s)  of 

the burner(s) clean may result in 

sooting and property damage.

Figure 34 - Injector Holder On Outlet 

Burner Tube

Burner 
Tube

Injector Holder (May 
Be Brass or Aluminum 
Depending on Model)

Primary Air Inlet Holes 
(Shape of Holes May 
Vary by Model)

f i r e - p a r t s . c o m

Summary of Contents for Comfort Glow CF26NTA

Page 1: ...y phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and serv...

Page 2: ...s an unvented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven ti...

Page 3: ...rtain you read and understand all warn ings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or its controls can be dangero...

Page 4: ...tilation to run properly This fireplace has an Oxygen Deple tion Sensing ODS safety shutoff system The ODS shuts down the fireplace if not enough fresh air is available See Air for Combustion and Vent...

Page 5: ...s are built more energy efficient than ever New materials increased insulation and new construction methods help reduce heat loss in homes Home owners weather strip and caulk around windows and doors...

Page 6: ...re considered a part of the uncon fined space Adjoining rooms are communicating only if there are doorless DETERMINING FRESH AIR FLOW FOR Fireplace LOCATION Determining if You Have a Confined or Uncon...

Page 7: ...two perma nent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see options 1 and 2 Figure 2 You can also remove door into adjoining room see...

Page 8: ...e minimum clearances shown in Figure4and5 page9 Ifyoucan providegreaterclearancesfrom floor ceiling and joining wall You can recess firebox into the wall You can also position fireplace in the optiona...

Page 9: ...42 365 8 257 8 513 4 267 8 Figure 6 Rough Opening for Installing in Corner 267 8 267 8 3 4 Off The Floor Minimum 10 1 2 Figure 5 Rough Opening for Installing in Wall Figure 4 Minimum Clearance for Co...

Page 10: ...the firebox front facing IMPORTANT Noncombustible materials such as brick tile etc may overlap the front facing but should never cover any necessary openings like louvered slots WARNING Do not allow n...

Page 11: ...shim in slot on mitered edge of side trim see Figure 9 6 While firmly holding edges of trim together tighten both set screws on the adjusting plate with slotted screwdriver 7 Repeat steps 1 through 6...

Page 12: ...nnection when servicingcontrols Wiringerrors cancauseimproperanddanger ous operation CAUTION Verify proper op eration after servicing Note If you are using a mantel with your heater use the following...

Page 13: ...onnect red wire to theAUTO switch posi tion Reconnect blue wire to the ON switch position Reconnect green and white wires to the power cord 10 Install the switch plate on the blower control shield wit...

Page 14: ...not included Outlet Receptacle Strain Relief Blue Red 1 Install a snap bushing found in hardware kit into one of the holes found on rear of blower control shield The other hole is for a strain relief...

Page 15: ...ent trap tee joint pipe wrench test gauge connection ACSAdesign certified equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the optional CSA desig...

Page 16: ...ied equipment shutoff valve from your dealer See Accessories page 27 Minimum inlet pressure for purpose of input adjustment 3 Minimum Gas Control Propane LP From External Regulator 11 W C to 14 W C Pr...

Page 17: ...l valve and equipment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where equipment shutoff valve was connecte...

Page 18: ...ernal joints for leaks 7 Turn off heater see To Turn Off Gas to Appli ance page 21 8 Replace front panel INSTALLING LOGS WARNING Failure to posi tion the parts in accordance with these diagrams or fai...

Page 19: ...shutoff valve is fully open 3 Turn control knob clockwise to the OFF position 4 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in...

Page 20: ...E 1 Follow steps 1 through 6 under Lighting Instructions page 19 2 Depress control knob and light pilot with match 3 Keep control knob pressed in for30 seconds after lighting pilot After 30 seconds re...

Page 21: ...t hair with a soft cloth or vacuum cleaner nozzle 5 Blow air into the primary air holes on the injector holder 6 In case any large clumps of dust have now been pushed into the burner repeat steps 3 an...

Page 22: ...1 Ignitor electrode not con nected to ignitor cable 2 Ignitor cable pinched or wet 3 Piezo ignitor nut is loose 4 Broken ignitor cable 5 Bad piezo ignitor 6 Ignitor electrode positioned wrong 7 Ignito...

Page 23: ...toff valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILOT position 4 Continue holding down con trol knob Repeat igniting op eration until air is removed 5 Contact local p...

Page 24: ...rner for dirt and debris If found clean burner see Cleaning and Mainte nance page 21 2 Replace gas control 3 Problem will stop after a few hours of operation 1 Refer to Air for Combustion and Ventilat...

Page 25: ...DS pilot seeCleaning and Maintenance page 21 1 Locate and correct all leaks see Checking Gas Connec tions page 17 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and...

Page 26: ...call DESA Heating Products at 1 866 672 6040 for referral information When calling DESA Heating Products have ready model number of your heater the replacement part number Parts Central These Parts C...

Page 27: ...SE Not Shown GMC83F Oak Finished Georgian Design CS26CP Black Red Oak Cottage Design GMC63UD Unfinished Traditional Design CMA208FB Light Oak Finished Traditional Design For all models Space saving ma...

Page 28: ...www desatech com 113896 01D 28 Illustrated Parts Breakdown Models CF26PTA and CF26NTA 12 9 10 11 16 20 18 1 8 5 4 7 6 19 13 19 14 2 19 19 3 15 17 19 fire parts com...

Page 29: ...nlet Tube 1 8 102983 06 Outlet Burner Tube 1 111331 08 Outlet Burner Tube 1 9 099056 29 Burner Orifice Injector 1 099056 20 Burner Orifice Injector 1 10 111124 01 Burner Retainer Spring 1 11 102980 01...

Page 30: ...www desatech com 113896 01D 30 ILLUSTRATED PARTS BREAKDOWN Models CF26PTA and CF26NTA 5 8 15 17 13 14 11 2 11 1 19 4 12 16 10 6 5 9 1 2 18 7 20 2 20 3 20 1 18 18 16 21 3 18 16 3 21 fire parts com...

Page 31: ...1 8 Bay Front Base 1 9 105421 01 Heat Deflector 1 10 105409 01 Fan Control Shield 1 11 1 105401 01 Screen Rod 1 11 2 105440 01 Screen Assembly 1 12 101386 02 Hinge 2 13 Rivets 8 14 105262 01CK Louver...

Page 32: ...ts related to repairing a defective fireplace will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRAN...

Reviews: