The space in the above example is a confined space 

because the actual Btu/Hr used is more than the maxi-

mum Btu/Hr the space can support. You must provide 

additional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an unconfined 

space, remove door to adjoining room or add 

ventilation grills between rooms. See 

Ventilation 

Air From Inside Building.

B.  Vent room directly to the outdoors. See 

Ventila-

tion Air From Outdoors

.

C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 

size makes room unconfined. 

If the actual Btu/Hr used is less than the maximum 

Btu/Hr the space can support,

 

the space is an un-

confined space. You will need no additional fresh 

air ventilation.

  WARNING:  If  the  area  in 

which the heater may be oper-

ated is smaller than that defined 

as an unconfined space or if the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3

 

or applicable local codes. 

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining 

unconfined space, you must provide two perma-

nent openings: one within 12” of the ceiling and 

one within 12” of the floor on the wall connecting 

the two spaces (see options 1 and 2, Figure 2). You 

can also remove door into adjoining room (see 

option 3, Figure 2). Follow the 

National Fuel Gas 

Code ANSI Z223.1/NFPA 54, Section 5.3, Air for 

Combustion and Ventilation

 for required size of 

ventilation grills or ducts. 

AIR FOR COMBUSTION 

AND VENTILATION

Continued

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or 

ducts. You must provide two permanent openings: 

one within 12” of the ceiling and one within 12” 

of the floor. Connect these items directly to the 

outdoors or spaces open to the outdoors. These 

spaces include attics and crawl spaces. Follow the 

National Fuel Gas Code ANSI Z223.1/NFPA 54, 

Section 5.3, Air for Combustion and Ventilation

 for 

required size of ventilation grills or ducts. 

IMPORTANT: 

Do not provide openings for inlet 

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the attic 

will activate the power vent.

Figure 2 - Ventilation Air from Inside 

Building Shown with Optional Mantel

Or 

Remove 

Door into 

Adjoining 

Room, 

Option 3

Ventilation Grills 

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room, 

Option 1

Figure 3 - Ventilation Air from Outdoors 

Shown with Optional Mantel

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To Attic

To

Crawl

Space

Summary of Contents for Comfort Glow CF26NRA

Page 1: ...light any appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot re...

Page 2: ...in an aftermarket per manently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indi cated on the rating plate This appliance i...

Page 3: ...ll warn ings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower...

Page 4: ...eds fresh air ventilation to run properly This replace has an Oxygen Deple tion Sensing ODS safety shutoff system The ODS shuts down the replace if not enough fresh air is available See Air for Combus...

Page 5: ...air for this and other fuel burning appliances in your home Today s homes are built more energy ef cient than ever New materials increased insulation and new construction methods help reduce heat loss...

Page 6: ...rnished with doors are considered a part of the uncon ned space Adjoining rooms are communicating only if there are doorless DETERMINING FRESH AIR FLOW FOR FIREPLACE LOCATION Determining if You Have a...

Page 7: ...rovide two perma nent openings one within 12 of the ceiling and one within 12 of the oor on the wall connecting the two spaces see options 1 and 2 Figure 2 You can also remove door into adjoining room...

Page 8: ...ARNING Maintainthemini mumclearancesshowninFigure 4 page 9 If you can provide greater clearances from oor ceiling and joining wall You can recess rebox into the wall You can also position replace in t...

Page 9: ...ble to Wall Minimum 16 inches from Side Wall Example 1 Frameinroughopening Usedimensionsshown in Figure 5 for the rough opening If installing in a corner use dimensions shown in Figure 6 for the rough...

Page 10: ...rlap the rebox front facing IMPORTANT Noncombustible materials such as brick tile etc may overlap the front facing but should never cover any necessary openings like louvered slots WARNING Do not allo...

Page 11: ...ting plate shim in slot on mitered edge of side trim see Figure 9 6 While rmly holding edges of trim together tighten both set screws on the adjusting plate with slotted screwdriver 7 Repeat steps 1 t...

Page 12: ...connection when servicingcontrols Wiringerrors cancauseimproperanddanger ous operation CAUTION Verify proper op eration after servicing Note If you are using a mantel with your heater use the followin...

Page 13: ...5 9 Reconnect red wire to theAUTO switch posi tion Reconnect blue wire to the ON switch position Reconnect green and white wires to the power cord 10 Install the switch plate on the blower control shi...

Page 14: ...nector not included Outlet Receptacle Strain Relief Blue Red 1 Install a snap bushing found in hardware kit into one of the holes found on rear of blower control shield The other hole is for a strain...

Page 15: ...supply an external regulator The external regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 14 inches of water If you do not reduce incoming gas pres...

Page 16: ...valve from your dealer See Accessories page 35 Minimum inlet pressure for purpose of input adjustment 3 Minimum Gas Control Propane LP From External Regulator 11 W C to 14 W C Pressure Natural From Ga...

Page 17: ...trol valve and equipment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where equipment shutoff valve was conne...

Page 18: ...diagrams or failure to use only parts speci cally approved with this heater may result in property damage or personal injury CAUTION After installa tion and periodically thereafter check to ensure tha...

Page 19: ...ne batteries Installing 9 Volt Battery in Receiver 1 Locate back of receiver under front burner of heater 2 Locate the battery clip mounted on the back of the receiver 3 Slide a 9 volt battery through...

Page 20: ...re equipment shutoff valve is fully open 3 Set switch in OFF position WARNING Burner will come on automatically within one minutewhentheselectorswitch is in the ON position after the pilot is lit 4 Pr...

Page 21: ...hrough 6 under Lighting Instructions page 20 2 Depress control knob and light pilot with match 3 Keep control knob pressed in for30 seconds after lighting pilot After 30 seconds release control knob N...

Page 22: ...for any reason cannot transmit to the receiver the receiver will shut off the replace after 8 minutes Key Pad Lock Feature This feature allows the user to lock unlock the keypad on the hand held remo...

Page 23: ...5 Figure 41 Correct Flame Pattern with Control Knob Set to High Flame Figure 42 Incorrect Flame Pattern with Control Knob Set to High Flame Approx 3 6 Above Top of Logs More Than 8 Above Top of Logs B...

Page 24: ...utes 2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt see Figure 43 3 Blow air through the ports slots and holes in the burner 4 Check the injector holder locate...

Page 25: ...nd base panel 4 Replace ignitor cable 5 Replace piezo ignitor 6 Replace pilot assembly 7 Replace pilot assembly 1 Turn on gas supply or open equipment shutoff valve 2 Turn control knob to PILOT positi...

Page 26: ...ully open equipment shutoff valve 4 A Contact local natural or propane LP gas company B Clean ODS pilot see Cleaning and Maintenance page 23 or replace ODS pilot assembly 5 Hand tighten until snug the...

Page 27: ...e burners until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum installation clearances see page 9 4 Clean burners see Cleaning and Maintena...

Page 28: ...ro pane LP gas company 3 CleanODS pilot seeCleaning and Maintenance page 23 1 Locate and correct all leaks see Checking Gas Connec tions page 17 2 Replace control valve 1 Take apart gas tubing and rem...

Page 29: ...Inlet Gas Pressure in of water Maximum 14 10 5 Minimum 11 5 Dimensions H x W x D Fireplace 25 7 8 x 27 x 13 3 4 25 7 8 x 27 x 13 3 4 Carton 28 x 26 13 16 x 16 1 2 28 x 26 13 16 x 16 1 2 Weight pounds...

Page 30: ...tech com 113897 01A 30 ILLUSTRATED PARTS BREAKDOWN MODELS CF26PRA AND CF26NRA 10 24 25 O F F P I L O T O N H I L O O F F P I L O T O N H I L O 16 15 19 8 19 20 21 17 18 14 13 23 12 22 13 4 7 6 9 5 11...

Page 31: ...80 01 102980 01 Burner 1 10 099387 13 099387 15 Pilot Tube 1 11 103781 02 103781 01 Gas Control Valve 1 12 103345 02 103345 02 Lower Bracket 1 13 M11084 38 M11084 38 Screw 8 x 38 7 14 104384 04 104384...

Page 32: ...www desatech com 113897 01A 32 ILLUSTRATED PARTS BREAKDOWN MODELS CF26PRA AND CF26NRA 5 8 15 17 13 14 11 2 11 1 19 4 12 16 10 6 5 9 1 2 18 7 20 2 20 3 20 1 18 18 16 21 3 18 16 3 21...

Page 33: ...er 1 8 105255 01 Bayfront Base 1 9 105421 01 Heat De ector 1 10 105409 01 Fan Control Shield 1 11 1 105401 01 Screen Rod 1 11 2 105440 01 Screen Assembly 1 12 101386 02 Hinge 2 13 099194 11 Rivets 8 1...

Page 34: ...uestions about installation operation or troubleshooting If so contact DESA Heating Products Technical Service Department at 1 866 672 6040 When calling please have your model and serial numbers of yo...

Page 35: ...g heater to be turned on and off by using a hand held remote control BRASS ACCENT TRIM GA7092 Not Shown Optional two piece trim kit for the Bayfront Fire place Easily screws to replace front Provides...

Page 36: ...such other costs related to repairing a defective replace will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EX...

Reviews: