OWNER’S MANUAL

 WARNING: Read all instruc-

tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property damage
or loss of life. Operation of im-
properly installed and maintained
venting system could result in
serious injury, property damage
or loss of life.

 WARNING: Seal all of the con-

nections with high temperature
silicone (600

°

F/316

°

 C) every time

a vent connection is made. Be-
fore joining elbows and pipes,
apply a bead of high temperature
silicone sealant (GE RTV 106/
Loctite RTV 81585) to the end of
the elbow or pipe. High tempera-
ture silicone must also be used to
re-seal any connections after
maintenance to venting system.

NOTICE: Failure to follow these
instructions will void the warranty.

INSTALLATION
PRECAUTIONS

Consult local building codes before beginning
the installation. The installer must make sure
to select the proper vent system for installa-
tion. Before installing vent kit, the installer
must read this fireplace manual and vent kit
instructions.

Only a qualified service person should in-
stall venting system. The installer must fol-
low these safety rules:

• Wear gloves and safety glasses for

protection

• Use extreme caution when using ladders

or when on roof tops

• Be aware of electrical wiring locations

in walls and ceilings

The following actions will void the war-
ranty on your venting system:

• Installation of any damaged venting

component

• Unauthorized modification of the vent-

ing system

VENTING
INSTALLATION

 WARNING: This gas fireplace

and vent assembly must be
vented directly to the outside.
The venting system must NEVER
be attached to a chimney serving
a separate solid fuel burning ap-
pliance. Each gas appliance must
use a separate vent system. Do
not use common vent systems.

 WARNING: Horizontal sec-

tions of this vent system require
a minimum clearance of 2" from
the top of the pipe and 1" mini-
mum to the sides and bottom.
Vertical sections of this system
require a minimum of 1" clear-
ance to combustible materials on
all sides of the pipe.

• Installation of any component part not

manufactured or approved by DESA
International

• Installation other than as instructed by

these instructions

INSTALLATION PLANNING

There are two basic types of direct-vent
installation:

• Horizontal Termination

• Vertical Termination

It is important to select the proper length of
vent pipe for the type of termination you
choose. It is also important to note the wall
thickness.

For Horizontal Termination:

 Select the

amount of vertical rise desired. The horizon-
tal run of venting must have 1/4" rise for
every 12" of run towards the termination.

NOTICE: Treatment of firestops
and construction of the chase
may vary from building type to
building type. These instructions
are not substitutes for the re-
quirements of local building
codes. You must follow all local
building codes .

Note:

 When installing in a chase, you should

insulate the chase as you would the outside
walls of your home. This is especially im-
portant in cold climates. Minimum clear-
ance between vent pipes and combustible
materials such as insulation is 1".

After framing the chase (see Framing and
Finishing
 on page 4) install the vent system
by following the installation instructions.

Installing Vent System in a Chase

A chase is a vertical box-like structure built
to enclose venting that runs along the out-
side of a building. A chase is not required for
such venting.

Continued

 WARNING: Never run the vent

downward as this may cause ex-
cessive temperatures which
could cause a fire.

You may use one or two 90

°

 elbows in this

vent configuration. See Horizontal Termina-
tion Configurations
 on pages 10 and 11.

For Vertical Termination:

 Measure the

distance from the fireplace flue outlet to the
ceiling. Add the ceiling thickness, the verti-
cal rise in an attic or second story, and allow
for sufficient vent height above the roofline.

You may use one or two 90

°

 elbows in this

vent configuration. See Vertical Termination
Configurations
 on pages 13 and 14.

Note:

 You may use two 45

°

 elbows in place

of a 90

°

 elbow. You must follow rise to run

ratios when using 45

°

 elbows.

For two-story applications, firestops are re-
quired at each floor level. If an offset is
needed in the attic, additional pipe and el-
bows will be required.

You may use a chase with a vent termination
with exposed pipe on the exterior of the
house. See Installing Vent System in a Chase,
below.

Your Comfort Glow direct-vent fireplace
has been tested for a minimum 3' rise with a
maximum 10" wall thickness. The maxi-
mum horizontal run is 20' with 8' vertical
rise (see Installation for Horizontal Termi-
nation
, page 8). The maximum vertical run
is 30' (see Installation for Vertical Termina-
tion
, page 12).

It is very important that the venting system
maintain its balance between the combus-
tion air intake and the flue gas exhaust.
Certain limitations apply to vent configura-
tions and must be strictly followed.

Summary of Contents for CHDV34(N/P)(A)

Page 1: ...istanceoradditionalinformation consult a qualified installer ser vice agency or the gas supplier This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by stat...

Page 2: ...indicated on fire place nameplate 14 This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electri cal Code ANS...

Page 3: ...replace has a piezo ignitor This sys tem requires no matches batteries or other sources to light fireplace Figure 1 Comfort Glow Direct Vent Fireplace CHDV Series Glass Door Assembly Blower Adjustment...

Page 4: ...e See Figure 3 20 34 3 4 5 8 for drywall facing Must maintain a minimum 1 clearance to combustibles 34 1 2 34 3 4 20 Vertical Termination 19 Horizontal Termination CLEARANCES Minimum clearances to com...

Page 5: ...be any obstruction such as bushes garden sheds fences decks or utility buildings within 24 from the front of the termination cap Do not locate termination cap where ex cessive snow or ice build up may...

Page 6: ...aved side walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minimum of 2...

Page 7: ...per length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount of vertical rise desired The horizon tal run...

Page 8: ...pipe and el bows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have four locking lugs indentations These lu...

Page 9: ...ition the vent cap in the center of the 7 1 2 or 10 hole on the exterior wall with the arrow on the vent cap pointing up Insure proper clearance of 1 to combustibles is maintained At tach the vent cap...

Page 10: ...Note This configuration for use with corner installation UP Horizontal Venting See information in Figures 16 and 17 for Vertical V and Horizontal H maxi mums and minimums The same amounts apply for f...

Page 11: ...max 8 min 8 min 20 max 20 max 8 max 20 max Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max 20 max 20 max Figure 19 Horizontal Termi...

Page 12: ...cutting loadbearing members Note Pay spe cial attention to these installation in structions for required clearances air space to combustibles when passing through ceilings walls roofs enclo sures att...

Page 13: ...tally using a level Temporarily tack the support box in place through the inside walls and into the roof sheathing 4 Using tin snips cut the supportbox from the top corners down to the roofline and fo...

Page 14: ...eleva tion above 4500 feet in Canada check with local authorities Consult your local gas company to help de termine the proper orifice for your location For assistance with any high altitude instal la...

Page 15: ...x 6 5 8 Number Description Available from DESA International SD2040 Simpson Dura Vent GS 30 Elbow 6 pcs SD2050 Simpson Dura Vent GS 60 Elbow 6 pcs Available from Simpson Dura Vent Only 902 7 x 48 Pip...

Page 16: ...system scirculatingblowerwhile using heater This will help circu late the heat throughout the house In the event of a power outage you can use this heater as your primary heat source NOTICE A qualifi...

Page 17: ...sup port bracket if exiting through the right side see Figure 33 Route power cord through both plastic bushing s and plug the power cord into a properly grounded 3 prong wall receptacle near the fireb...

Page 18: ...tor if allowed by local codes not provided AnA G A design certifiedmanualshutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Pur chase the A G A design certified manua...

Page 19: ...e provided by installer from manual shutoff valve to fireplace Route flexible gas supply line through one of the access holes on side of fireplace 3 Attach flexible gas line from gas sup ply to contro...

Page 20: ...e see Fig ure 37 2 Open propane LP supply tank valve for propane LP fireplace or main gas valve located on or near gas meter for natu ral gas fireplace 3 Make sure control knob of fireplace is in the...

Page 21: ...the top and bottom of glass door frame INSTALLING OPTIONAL WIRELESS HAND HELD REMOTE CONTROL CGHRC SERIES CGHRCT SERIES Installing Remote Receiver 1 Open bottom louver and locate the switch bracket o...

Page 22: ...ely secure retainer brackets to grate Brackets are adjustable left to right to allow proper placement of panel These will hold rear panel in place while installing side panels 5 Install left side bric...

Page 23: ...log as shown in Figure 50 4 Place log 4 right log onto the front left part of the grate making sure the notches fits over the prong of the grate see Figure 51 5 Place lava rock along sides and front o...

Page 24: ...ighting 8 Turn knob on gas control counter clockwise to PILOT 9 Push in control knob all the way and hold Immediately light the pilot by repeatedly depressing the piezo spark ignitor until a flame app...

Page 25: ...not leave the selec tor switch in the REMOTE position when the pilot is not lit This will drain the battery IMPORTANT Be sure to press the ON OFF buttons on the hand held remote control unit for up t...

Page 26: ...or the proper flame height Alterations may have occurredduringshippingandhandling Call a qualified service person to readjust the pilot if necessary The height of the thermopile must be 3 8 to 1 2 abo...

Page 27: ...and fittings and can be caused by having excessive lateral runs too many el bows or exterior portions of the sys tem being exposed to cold weather 4 Inspect joints to verify that no pipe sec tion or f...

Page 28: ...rmocouple connection loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable d...

Page 29: ...moved from line Have gas line checked by local pro pane LP gas company 3 Clean burner see Cleaning and Mainte nance page 27 or replace burner orifice 1 Adjust the log set so that the flame does not ex...

Page 30: ...nt above 1 Improper log placement 2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when cont...

Page 31: ...0 337 2564 You can also visit DESA International s Technical Service web site at www desatech com REPLACEMENT PARTS Figure 58 Blower Wiring Diagram for Thermostat Controlled Models WIRING DIAGRAM CAUT...

Page 32: ...HDV34 N P A ILLUSTRATED PARTS BREAKDOWN CHDV34N A 1 2 3 4 6 6 39 5 5 6 5 11 Included in Hardware Pack 7 7 8 10 9 12 13 14 15 16 17 18 19 20 35 21 22 23 24 25 26 27 28 28 29 30 34 1 34 4 34 2 34 3 36 3...

Page 33: ...ilot Natural 1 19 104498 01 Thermocouple 1 20 104499 01 Thermopile 1 21 104500 01 Ignitor 1 22 104501 01 Ignitor Bracket 1 23 104502 01 Ignitor Screw 1 24 104503 01 Ignitor Wire 1 25 104504 01 Burner...

Page 34: ...CHDV34 N P A ILLUSTRATED PARTS BREAKDOWN CHDV34P A 1 2 3 4 6 6 39 5 5 6 5 11 Included in Hardware Pack 7 7 8 10 9 12 13 14 15 16 17 18 19 20 35 21 22 23 24 25 26 27 28 28 29 30 34 1 34 4 34 2 34 3 36...

Page 35: ...104497 02 SIT Pilot Propane LP 1 19 104498 01 Thermocouple 1 20 104499 01 Thermopile 1 21 104500 01 Ignitor 1 22 104501 01 Ignitor Bracket 1 23 104502 01 Ignitor Screw 1 24 104503 01 Ignitor Wire 1 25...

Page 36: ...glass panel with in cluded clips RECEIVER AND HAND HELD ON OFF REMOTE CONTROL KIT CGHRC SERIES For all models Allows the heater to be turned on and off conveniently RECEIVER AND HAND HELD THERMOSTAT R...

Page 37: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 38: ...ring a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED...

Reviews: