background image

4

103569

VENT-FREE PROPANE/LP GAS HEATER

BLUE-FLAME CGP20, CGP20L AND RP30D

Continued

 

 WARNING: If the area in

which the heater may be oper-
ated is smaller than that defined
as an unconfined space, provide
adequate combustion and venti-
lation air by one of the methods
described in the 

National Fuel

Gas Code, ANSI Z223.1, 1992,
Section 5.3 or applicable local
codes.

 WARNING: Rework work-

sheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING AIR FLOW
FOR HEATER LOCATION

Determining if You Have a
Confined or Unconfined Space

Use this worksheet to determine if you have
a confined or unconfined space.

Space:

 Includes the room in which you

will install heater plus any adjoining rooms
with doorless passageways or ventilation
grills between the rooms.

1.

Determine the volume of the space
(length x width x height).

Length x Width x Height =
___________cu. ft. (volume of space)

Example: 

Space size 20 ft. (length) x

16 ft. (width) x 8 ft. (ceiling height) =

2560 cu. ft. (volume of space)

If additional ventilation to adjoining
room is supplied with grills or open-
ings, add the volume of these rooms to
the total volume of the space.

2.

Divide the space volume by 50 cubic
feet to determine the maximum Btu/Hr
the space can support.

______(volume of space) 

÷

 50 cu. ft. =

(Maximum Btu/Hr the space can sup-
port)

Example:

  2560 cu. ft. (volume of

space) 

÷

 50 cu. ft. = 51.2 or 51,200

(maximum Btu/Hr the space can sup-
port)

3.

Add the Btu/Hr of all fuel burning ap-
pliances in the space.

Vent-free heater _________ Btu/Hr

Gas water heater*________ Btu/Hr

Gas furnace ____________ Btu/Hr

Vented gas heater ________ Btu/Hr

Gas fireplace logs ________ Btu/Hr

Other gas appliances*+____ Btu/Hr

Total                          = ____ Btu/Hr

Example:

Gas water heater

40,000 Btu/Hr

Vent-free heater +

20,000 Btu/Hr

Total                  =

60,000 Btu/Hr

* Do not include direct-vent gas appli-
ances. Direct-vent draws combustion
air from the outdoors and vents to the
outdoors.

4.

Compare the maximum Btu/Hr the
space can support with the actual
amount of Btu/Hr used.

__________ Btu/Hr (maximum the
space can support)

___________ Btu/Hr (actual amount of
Btu/Hr used)

Example:

  51,200 Btu/Hr (maximum

the space can support)

60,000 Btu/Hr (actual amount of
Btu/Hr used)

The space in the above example is a con-
fined space because the actual Btu/Hr used
is more than the maximum Btu/Hr the space
can support. You must provide additional
fresh air. Your options are as follows:

A. Rework worksheet, adding the space of

an adjoining room. If the extra space
provides an unconfined space, remove
door to adjoining room or add ventila-
tion grills between rooms. See Ventila-
tion Air From Inside Building
.

B. Vent room directly to the outdoors. See

Ventilation Air From Outdoors, page 5.

C. Install a lower Btu/Hr heater, if lower

Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the
maximum Btu/Hr the space can support, the
space is an unconfined space. You will need
no additional fresh air ventilation.

VENTILATION AIR

Ventilation Air From Inside
Building

This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must pro-
vide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2 page 5). You
can also remove door into adjoining room
(see option 3, Figure 2). Follow the National
Fuel Gas Code NFPA 54/ANSI Z223.1, Sec-
tion 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or
ducts.

Summary of Contents for CGP20

Page 1: ...apors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building...

Page 2: ...g WARNING ICON G 001 WARNINGS DANGER Carbon monoxide poisoning may lead to death WARNING Anychangetothis heater or its controls can be dan gerous 2 Do not place propane LP supply tank s inside any str...

Page 3: ...space Adjoining rooms are communicating only iftherearedoorlesspassagewaysorventila tion grills between them WARNING This heater shall not be installed in a confined space unless provisions are pro vi...

Page 4: ...gas heater ________ Btu Hr Gas fireplace logs ________ Btu Hr Other gas appliances ____ Btu Hr Total ____ Btu Hr Example Gas water heater 40 000 Btu Hr Vent free heater 20 000 Btu Hr Total 60 000 Btu...

Page 5: ...Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two per manent openings one within 12 of the ceiling and one within 12 of the floor Connect these items...

Page 6: ...onnection see Figure 13 page 9 sediment trap tee joint pipe wrench AnA G A design certified manual shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Pur chase the op...

Page 7: ...nchor method For attaching mounting bracket to hollow walls wall areas between studs or solid walls concrete or masonry 1 Drill holes at marked locations using 5 16 drill bit For solid walls concrete...

Page 8: ...st gauge hook up NPT tap must be upstream from heater see Figure 13 page 9 Apply pipe joint sealant lightly to male threads This will prevent excess sealant from going into pipe Excess sealant in pipe...

Page 9: ...em Pressures in excess of 1 2 PSIG will damage heater regulator 2 Cap off open end of gas pipe where manual shutoff valve was connected 3 Pressurize supply piping system by ei ther using compressed ai...

Page 10: ...s appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions ex actly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to...

Page 11: ...flame pattern and burner flame pattern often PILOT FLAME PATTERN Figure 18 shows a correct pilot flame pat tern Figure 19 shows an incorrect pilot flame pattern The incorrect pilot flame is not touchi...

Page 12: ...tionlooseatcon trol valve 5 Pilotflamenottouchingthermocouple which allows thermocouple to cool causing pilot flame to go out This problemcouldbecausedbyoneorboth of the following A Low gas pressure B...

Page 13: ...n heater blocked 4 Dirty or partially clogged burner ori fice Continued REMEDY 1 Contactlocalpropane LPgascompany 2 Clean burner see Cleaning and Main tenance page 15 or replace burner orifice 1 Clean...

Page 14: ...rtially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Notenoughc...

Page 15: ...propane LP gas supply may be low When gas quality is bad pilot will not stay lit burner will produce flames and soot heater will backfire when lit Youmayfeelyourgaspressureistoolowor gas quality is ba...

Page 16: ...placementpartsandaccessories Whencall ing a Parts Central ask for the Parts Depart ment Baltimore Electric 1348 Dixwell Avenue Hamden CT 06514 1 800 397 7553 203 248 7553 Parts Department Portable He...

Page 17: ...AL SHUTOFFVALVE GA5010 For all models Manual shutoff valve with 1 8 NPT tap FLOOR MOUNTING STAND 20 000 Btu Hr Models CGP20L GA4500L Ivory CGP20 GA4500 Earthtone For locating heater on the floor away...

Page 18: ...103569 VENT FREE PROPANE LP GAS HEATER BLUE FLAME CGP20 CGP20L AND RP30D 1 2 4 5 6 7 8 8 9 10 11 12 15 17 19 21 22 23 24 20 27 26 18 14 16 25 3 13 ODS PILOT 10 1 10 2 ILLUSTRATED PARTS BREAKDOWN RP30...

Page 19: ...1 098514 01 Thermocouple 1 10 2 098594 01 Ignitor Electrode 1 11 103447 01 Burner 1 12 099387 05 3 16 Pilot Tubing 1 13 103845 03 Injector 1 14 099066 01 Mounting Bracket 1 15 099415 06 Pressure Regul...

Page 20: ...VENT FREE PROPANE LP GAS HEATER BLUE FLAME CGP20 CGP20L AND RP30D ODS PILOT 12 1 12 2 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 17 19 27 21 23 24 25 26 22 29 28 20 16 18 15 ILLUSTRATED PARTS BREAKDOWN CGP2...

Page 21: ...M5 2 12 099059 04 ODS Pilot Assembly 1 12 1 098514 01 Thermocouple 1 12 2 098594 01 Ignitor Electrode 1 13 103446 01 Burner 1 14 099387 05 3 16 Pilot Tubing 1 15 103845 01 Injector 1 16 099066 01 Mou...

Page 22: ...____________________________________________ _______________________________________________________________________________________________ ___________________________________________________________...

Page 23: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 24: ...is warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance o...

Reviews: