MOUNTING INSTRUCTIONS
Free the diffusion plenum from its packaging;
Remove the delivery air outlets and the closing panel from the plenum;
Place the plenum on the top of the equipment;
Fix the plenum to the equipment using the screws provided, entering through the delivery outlet openings and the
closing panel;
Remount the delivery outlets and the closing panel.
WARNING!
The plenum top surface cannot be walked on.
THROW DISTANCE
The scheme shows the throw distances in metres at which the remaining velocity is reduced to 0.1 m/s depending on the
inclination of the fins per individual plenum with one, two or three openings.
Opening on 2 sides
Opening on 3 sides
Opening on 4 sides
Fin inclination
0°
20°
30°
45°
0°
20°
30°
45°
0°
20°
30°
45°
1
44 35 28 21 36 29 23 17 31 25 20 15
2
42 33 27 20 34 27 22 16 29 24 19 14
3
48 39 31 23 40 31 26 19 35 28 22 16
4
48 39 31 23 40 31 26 19 35 28 22 16
5
59 46 38 28 48 38 31 23 42 33 27 20
6
75 60 48 36 61 48 40 29 54 43 33 25
7
82 65 53 39 67 53 44 32 58 47 38 27
8
93 74 60 45 76 60 49 36 66 54 44 32
9
106 80 63 46 82 63 52 39 68 54 45 34
10
112 88 72 54 91 72 59 43 79 63 51 38
11
104 82 68 56 79 66 54 45 70 55 45 37
12
122 97 80 66 98 77 64 53 81 64 53 44
13
147
116 96 80 118 93 77 64 98 77 64 53
14
147
116 96 80 118 93 77 64 98 77 64 53
15
164 134 116 102 134 106 95 76 116 89 74 61
WARNING!
It is not allowed to have air diffused from one side only of the plenum.