VENT FREE PROPANE/LP GAS HEATER

BLUE FLAME 6000 BTU/HR

CONNECTING TO
GAS SUPPLY

NOTICE: A qualified service per-
son must connect heater to gas
supply. Follow all local codes.

The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure between 11 and 14
inches of water. If you do not reduce incom-
ing gas pressure, heater regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
12. Pointing the vent down protects it from
freezing rain or sleet.

 CAUTION: Never connect

heater directly to the propane/LP
supply. This heater requires an
external regulator (not supplied).
Install the external regulator be-
tween the heater and propane/LP
supply.

Propane/LP
Supply Tank

Figure 12 - External Regulator With Vent
Pointing Down

 CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe 3/8"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.

IMPORTANT:

  Hold pressure regulator

with wrench when connecting it to gas pip-
ing and/or fittings.

Figure 13 - Gas Connection

*  An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual
shutoff valve from your dealer. See Accessory, page 15.

Tee Joint

Reducer
Bushing to
1/8" NPT

1/8" NPT
Plug Tap

Test

Gauge

Connec-

tion *

Heater
Cabinet

Pressure
Regulator

Tee
Joint

Pipe
Nipple

Cap

Ground Joint Union

3/8" NPT
Pipe Nipple

Sediment

Trap

3" Minimum

Manual Shutoff Valve *

From External

Regulator

(11" W.C. to 14"

W.C. Pressure)

External
Regulator

Install sediment trap in supply line as shown
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

Installation must include a manual shutoff
valve, ground joint union, and plugged
1/8" NPT tap. Locate NPT tap within reach
for test gauge hook up. NPT tap must be
upstream from heater (see Figure 13).

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

 CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

Vent
Pointing
Down

Summary of Contents for 6000 BTU/HR

Page 1: ...r call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from t...

Page 2: ...hbor s phone Follow the gas supplier s instructions if you cannot reach your gas supplier call the fire department 4 Never install the heater in a recreational vehicle where curtains furniture clothin...

Page 3: ...ew materials increased insulation and new construction methods help reduce heat loss in homes Home own ers weather strip and caulk around windows and doors to keep the cold air out and the warm air in...

Page 4: ...plates and floors between wall ceil ing joints between wall panels at penetrations for plumbing electrical and gas lines and at other openings If your home meets all of the three criteria above you m...

Page 5: ...ze of ventilation grills or ducts WARNING Rework worksheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both spaces Fig...

Page 6: ...TING HEATER This heater is designed to be mounted on a wall WARNING Maintainthemini mumclearancesshowninFigure 4 Ifyoucan providegreaterclear ances from floor ceiling and joining wall Forconveniencean...

Page 7: ...ace Thin or Thick Wall thick wall shown Solid Wall Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place large openings of slots over screwheads Sli...

Page 8: ...o gas pip ing and or fittings Figure 13 Gas Connection An A G A design certified manual shutoff valve with 1 8 NPT tap is an acceptable alternativetotestgaugeconnection PurchasetheoptionalA G A design...

Page 9: ...k all joints from manual shutoff valve to control valve see Figure 15 Apply mixture of liquid soap and wa ter to gas joints Bubbles forming show a leak 5 Correct all leaks at once 6 Light heater see O...

Page 10: ...r button This will light pilot The pilot is attached to the front of burner The pilot can be seen through the glass panel If needed keep pressing ignitor button until pilot lights OPERATING HEATER Con...

Page 11: ...nerFlamePattern Ifburnerflamepatternisincorrect asshown in Figure 21 turn heater off see To Turn Off Gas to Appliance page 10 see Troubleshooting pages 12 through 14 Yellow Tipping CLEANING AND MAINTE...

Page 12: ...he following A Low gas pressure B Dirty or partially clogged ODS pilot 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignito...

Page 13: ...page 11 2 Contact local propane LP gas company 3 Replace gas regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to LOW position and let warm up for a minute 2 Operate bu...

Page 14: ...ers If noise is excessive contact qualified ser vice person 1 Ventilate room Stop using odor causing products while heater is running 2 Refill supply tank 3 Locate and correct all leaks see Check ing...

Page 15: ...ss listed on the back page of this manual Send a check for 5 00 payable to DESA International Purchase this heater accessory from your local dealer If they cannot supply this ac cessory call DESA Inte...

Page 16: ...2 VENT FREE PROPANE LP GAS HEATER BLUE FLAME 6000 BTU HR 10 12 11 1 2 3 4 5 6 7 9 8 10 13 14 15 16 17 18 21 23 24 27 22 26 25 19 20 28 29 HEATER EXPLODED VIEW 12 2 12 1 ODS PILOT VP600B ILLUSTRATED PA...

Page 17: ...le 1 11 098249 01 Nut M5 2 12 099059 03 ODS Pilot Assembly 1 12 1 098514 01 Thermocouple 1 12 2 098594 01 Ignitor Electrode 1 13 099386 02 Burner 1 14 099387 05 Pilot Tubing 1 15 098251 08 Injector 1...

Page 18: ..._______________________________________ _______________________________________________________________________________________________ ________________________________________________________________...

Page 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 20: ...swarranty Theheater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in origina...

Reviews: