68
DENT Instruments
PowerScout HD
RTU Programming & Scripting
2 Wire 1
ɸ
(
Plug Load)
Service Type
3
V_Input
1
or 2
Description
31 Char
Channels
Volt Ref
CT Type
Range
Phase Shift CT Multiplier
CT Sign
CH1
ANY
[1-6]
mV
[1]
or
RōCoil
[2]
Any > 0A
-4.0
˚
to +4.0
˚
Any > 0
[1]
0 or 1
CH2
ANY
[1-6]
mV
[1]
or
RōCoil
[2]
Any > 0A
-4.0
˚
to +4.0
˚
Any > 0
[1]
0 or 1
CH3
ANY
[1-6]
mV
[1]
or
RōCo
il
[2]
Any > 0A
-4.0
˚
to +4.0
˚
Any > 0
[1]
0 or 1
Any channel that needs to be turned OFF should set the CT Type to OFF [0].
3 Wire 1
ɸ
(Split Phase)
Service Type
4
V_Input
1
or 2
Description
31 Char
Channels
Volt Ref
CT Type
Range
Phase Shift CT Multiplier
CT Sign
CH1
L1 – N
[1]
mV
[1]
or
RōCoil
[2]
Any > 0A
-4.0
˚
to +4.0
˚
Any > 0
[1]
0 or 1
CH2
L2 – N
[2]
mV
[1]
or
RōCoil
[2]
Any > 0A
-4.0
˚
to +4.0
˚
Any > 0
[1]
0 or 1
CH3
L3 – N
[3]
OFF
[0]
Any > 0A
-4.0
˚
to +4.0
˚
Any > 0
[1]
0 or 1
Even though CH3 is not used for computation it is recommended that the CT settings reflect those from CH1 rather than being left at factory
default to facilitate configuration validation from the RTU.
Disabled
(OFF)
Service Type
5
V_Input
1
or 2
Description
31 Char
Channels
Volt Ref
CT Type
Range
Phase Shift CT Multiplier
CT Sign
CH1
L1 – N
[1]
OFF
[0]
Any > 0A
-4.0
˚
to +4.0
˚
Any > 0
[1]
0 or 1
CH2
L2 – N
[2]
OFF
[0]
Any > 0A
-4.0
˚
to +4.0
˚
Any > 0
[1]
0 or 1
CH3
L3 – N
[3]
OFF
[0]
Any > 0A
-4.0
˚
to +4.0
˚
Any > 0
[1]
0 or 1
Even though disabled channels are not used in calculations and report 0.0 they still contain configuration information. It is suggested that they
be set to a known value rather than left at defaults to facilitate configuration validation by the RTU.
www.
.com
1.800.561.8187