46
DENT Instruments
PowerScout HD
Meter Installation
Wiring the PSHD Meter in a Single-Phase Application
The PSHD meter is internally powered through the voltage between L1 and L2. For Single Phase
installations where no L2 exists it is advised to jumper N to L2. This connection provides power to the
meter while maintaining Neutral as the metering voltage reference.