Set pump to compensate at minimum psi. Check and record replenishing and ser vo
pressure.
Servo pressure - minus replenish pressure:
30/24 series: 160 to 220 psi, 11 to 15 bar
*Replenish pressure - minus case pressure:
Std –30/24 series: 180 to 220 psi, 12,4 to 15,2 bar
“S” version: 330 to 370 psi, 23-26 bar
If pressures are incorrect, remove replenishing relief valve pilot and increase or
decrease pressure as required. One full turn on adjusting screw will cause pressure to
change approximately 25 psi, 1,7 bar. Re-torque locknut to 20-25 lbs-in., 2,3-2,8 Nm.
*Replenish pressure may be set to customer requirement, not to e xceed 450 psi,
31 bar.
NOTE: There is no servo relief valve adjustment. Increasing or decreasing
replenishing pressure will cause both servo and replenishing pressure to
change by the same amount.
Set the pump to compensate at 5000 psi, 345 bar record replenishing and ser vo
pressures.
Servo pressure- minus replenish pressure:
24 series: 360 to 420 psi, 24,8 to 30 bar
30 series: 472 to 532 psi, 32,5 to 37 bar
Replenish pressure - minus case pressure:
Std–24 series: 180 to 220 psi, 12,4-15,2 bar
30 series: 200 to 240 psi, 14 to 17 bar
“S” version: 330 to 370 psi, 23-26 bar
Set pump to compensate at minimum psi. Servo pressures should return to the values
of the previous step.
NOTE: After completing last step, proceed with pump control test,
refer to control
service manual S1-AM030
. Continue with the next steps after controls testing.
Adjust pump displacement for full volume and adjust system pressure to 5000 psi,
345 bar. **Adjust compensator from 5000 psi, 345 bar to minim um pressure in
1000 psi, 69 bar intervals. At each pressure, stroke rotary servo input shaft to the full
position on each side of center. Cam indicator should remain on or very near the
zero position with no oscillation. System pressure should not vary from port “A” to
port “B” more than 150 psi, 10,3 bar and not oscillate .
CAUTION:
Do not hold pump at 5000 psi, 345 bar f or longer than one minute at any
time. This is only an intermittent pressure rating.
Minimum compensator pressure should be under 500 psi, 34,5 bar .
Increase compensator adjustment to1000 psi, 70 bar and increase and decrease sys-
tem pressure above and below compensator setting. When system pressure is above
compensator setting, the pump should de-stroke and not oscillate. When the system
pressure is below the compensator setting the pump should strok e to full volume.
Repeat at 5000 psi, 345 bar.
Check pump for external leaks. No external leaks permitted.
After all tests are completed re-torque main housing bolts to 350 lbs-ft., 476 Nm.
The following test procedure may be used if the standard closed loop test stand is not
available.
Maximum runout between pump shaft and electric motor shaft 0.003”, 0,076 mm total
indicator reading.
Electric motor speed - 1800 r pm.
Inlet temperature - 120
0
-140
0
F., 500-580C.
Inlet condition - main pump - 24 ser ies 150 psi min., 10,3 bar
30 series 225 psi min., 15,5 bar
Internal vane pump - 10”, 254 mm Hg to 5 psi, 0.34 bar
Case pressure 55 - 75 psi, 3,8 - 5,2 bar (e xcept “S” pump)
Fluid - 200 SSU at 100
0
F., 46 cSt at 40°C
TEST PROCEDURE
BASIC PUMP TEST
(continued)
ALTERNATE TEST PROCEDURE
GENERAL REQUIREMENTS
38
www.comoso.com