Shipping and Storage
CAIR
plus
22
PR-2009-0096-GB • Subject to modifications • R8-10/2015
4.3
Storage
•
Always place units on an even surface for storage or intermediate storage.
•
Protect units from bumps and knocks which may damage the casing and protruding
components.
•
If commissioning is not carried out within three months following the delivery, the belt
drive must be slackened.
•
Rotate the motor axis and fan through at least 2 revolutions every 3 months.
4.3.1 Permitted storage conditions / permitted air condition for non-installed units
Air temperature
-10 °C to +50 °C
Air humidity
Store units in a dry, non-condensing atmosphere
Notice!
•
Observe the permissible storage conditions when storing the unit. Remove the
original packaging only before installation.
•
If the unit is stored for a period of time before installation or commissioning,
protect it from damage through elements, build-up of dust and dirt!
•
Prior to commissioning, take appropriate measures to protect units without
packaging against build-up of dust and dirt. If packing takes place on site by
others, make sure that condensate cannot form below the packaging (consider
relevant clearance between the packaging and casing).