MAINTENANCE

The dryers require little maintenance for satisfactory 

operation. Good dryer performance can be expected if 

the following routine maintenance steps are taken.

Daily Maintenance

Check the separator for condensate discharge. If no 

discharge is evident, depressurize and dismantle.  Clean 

separator housing with mild soap and water. Discard 

automatic float drain and replace.

Monthly Maintenance

Inspect the condenser coils. Remove accumulated dust 

and dirt with a soft brush or with air from an OSHA 

approved compressed air nozzle that limits the discharge 

pressure to 30 psig.

General

For continued good performance of your refrigerated 

dryer, all refrigeration system maintenance should be 

performed by a competent refrigeration mechanic.

NOTE:

 Before corrective maintenance is done during the 

warranty period, call your local distributor and proceed 

according to instructions. Refer to the warranty for limits 

of your coverage.

Parts List

Item

All Models

On/Off Switch

3245021

Float Drain Kit

3090900

Returns to Manufacturer

If the dryer or a component of the dryer must be 

returned to the manufacturer, first call your local 

distributor for a return authorization number and 

shipping address. Your distributor will inform you whether 

the dryer or only a component must be returned. Mark 

the package with the return authorization number and 

ship freight prepaid as directed by your local distributor.

Summary of Contents for HG 5-10

Page 1: ...N 2 RECEIVING MOVING AND UNPACKING 2 INSTALLATION 3 INSTRUMENTATION 4 CONDENSATE DRAIN VALVES 4 START UP OPERATION 4 SHUTDOWN 4 MAINTENANCE 5 FIELD SERVICE GUIDE 6 ENGINEERING DATA 7 ELECTRICAL SCHEMATIC 7 AIR AND REFRIGERANT FLOW SCHEMATIC 7 WARRANTY 8 3252442 Rev B 2 09 INSTRUCTION MANUAL Models HG 5 10 HG 15 ...

Page 2: ...ations for the requirements for breathing quality air RECEIVING MOVING AND UNPACKING A RECEIVING This shipment has been thoroughly checked packed and inspected before leaving our plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist that a notation of this l...

Page 3: ... Most compressed air systems require filters for removal of solid and liquid contaminants When an oil removal filter is used it should be installed downstream of the refrigerated dryer The dryer will remove some entrained dirt extending the life of the replaceable filter element Outlet air temperature may be 10 to 30 degrees higher than inlet air temperature This is normal Consult your distributor...

Page 4: ...lighted switch is glowing If light is not glowing unplug unit and refer to Field Service Guide for additional information or call your local distributor b Confirm that condensate is discharging from the drain This can only be done when there is air flow through the dryer Reference Serial Number Tag for appropriate power requirement connection rating Make other dryer connections prior to connecting...

Page 5: ...nued good performance of your refrigerated dryer all refrigeration system maintenance should be performed by a competent refrigeration mechanic NOTE Before corrective maintenance is done during the warranty period call your local distributor and proceed according to instructions Refer to the warranty for limits of your coverage Parts List Item All Models On Off Switch 3245021 Float Drain Kit 30909...

Page 6: ...rator drain trap Failure of drain trap Replace float mechanism SYMPTOM Dryer inlet air temperature too high Aftercooler malfunction Check aftercooler discharge temperature and reduce to dryer design condition 122 F max SYMPTOM Refrigerant compressor stopped Leak in refrigerant system Consult local distributor Compressor overheated Turn dryer off wait 30 minutes turn dryer on Motor thermostat self ...

Page 7: ... Height inches 15 4 15 4 Length inches 12 6 12 6 Width inches 12 6 12 6 Power Supply V Ph Hz 115 1 60 115 1 60 Refrigerant Compressor Rating hp 1 8 1 7 Input Power kW 0 21 0 24 Refrigerant Typeb R 134a R 134a MINIMUM MAXIMUM OPERATING CONDITIONS Min Max Inlet Air Pressure compressed air at inlet to dryer 30 250 psig 30 250 psig Min Max Inlet Air Temperature compressed air at inlet to dryer 40 F 12...

Page 8: ... to the original product The foregoing is the exclusive remedy of any buyer of the manufacturer s product The maximum damages liability of the manufacturer is the original purchase price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSED IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED ...

Reviews: