DPM-12GM-6-P1A-FP10-F-V1 10/31/2018
12
ROCON LLC
INSTALLATION
1. DeltaPoint unit is preferred to be mounted on the outside of the fence line, for ease of service.
2. DeltaPoint can be mounted in any orientation: horizontally, vertically or at any other angle. The
orientation has no effect on performance. It is suggested that unions or hosing be used when
connecting to the main supply and return piping, this will facilitate ease of maintenance or removal
of unit if needed.
Caution:
Brass pipe nipples installed on the “Supply” and “From Cell” ports cannot be removed.
They are needed for proper operation of the flow sensors
3. See
DIMENSIONS
for mounting hole pattern.
4. Connecting fluid ports: The unit has ¾-
inch NPT female pipe ports. Port 1 “SUPPLY” cooling water
into the unit, Port 2 “TO CELL” cooling water to tooling or robot, Port 3 “FROM CELL” returns water
from the cell or robot. Port 4 “RETURN” cooling water leaving the DeltaPoint unit.
5. Units can be installed where the pipe or hose diameter is larger than the port size. Do not exceed
1-inch pipe or hose diameter with the 12 GPM unit.
Caution:
Water flow cannot exceed 15 GPM for a 12 GPM unit.
6. Open the water inlet ball valve SLOWLY to prevent water hammer damage to the SENSORS.
7. Connect the electrical power and PROFINET cables. All units have an Electrical Callout Tag
reference page 20 that describes the pin number, location, wire color and function.