VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-80
There are speed LOOP and position LOOP in position mode. This parameter is used to
adjust gain of speed LOOP (FX 10-22).
10-23
PG Position Attained 2
a
Factory setting 100
Settings
0~20000
It is used to set the range of position attained in P2P mode.
10-24
P2P Acceleration Time
a
Factory setting 1.00
Settings
0.00~100.00
s
10-25
P2P Deceleration Time
a
Factory setting 1.00
Settings
0.00~100.00
s
10-26
Delay Time for Position Command
a
Factory setting 0.005
Settings
0.00~100.00
s
10-27
Position Control P Gain 2
a
Factory setting 50.0
Settings
0.0~1500.0%(05-25
switch)
10-28
Position Control Integral (I) Time 2
a
Factory setting 0.050
Settings
0.001~10.000
s
0.000: no integral(0.5-25 switch)
10-29
Selection of P2P Control Mode
a
Factory setting 00000
Settings
0: relative P2P
1: absolute P2P
It is used to position control of point to point. There are two modes (relative and absolute)
for selection.
10-30
Direction Command of Absolute P2P
a
Factory setting
0
Settings
0~255 (10-33~40)
It is used to set the direction in absolute P2P mode. (the direction is determined by main
control command in relative P2P mode)
10-31
FWD Limit of Absolute P2P
a
Factory setting
0
Settings
0: No Limit
1~60000
Summary of Contents for VFD-V Series
Page 1: ......
Page 2: ...V E 0 5 5011608405 2016 04...
Page 3: ......
Page 7: ......
Page 27: ......
Page 31: ......
Page 115: ......
Page 121: ......
Page 153: ......
Page 159: ...VFD V Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED B 4 Braking Resistors Braking Units...
Page 160: ...B VFD V Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED B 5 Braking Resistors Braking Units...
Page 173: ......
Page 183: ......