Chapter 5 Parameters
|
VFD-M-D Series
5-50
Revision Jan. 2007, MDE2, SW V1.05
For example: if Pr.4-05=3, Pr.4-23=2, then the total door close acceleration time =3+(2*2)=7
sec (To calculate with F=60Hz, if F=30, the total acceleration time will be reduced by half)
If Pr.4-23 is larger than Pr.4-05, the total acceleration time=
4-05*4-23
2*
Timing diagram for multi-step door close
1.
Multi-step mode 1 (Pr.0-09=2)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
FWD
MI1
MI2
MI3
05-00=1
05-01=2
05-02=3
MI4
05-03=4
RE V
B
05-05=18
Door Close Limit
16th step
5-32
15th s tep
5-31
14th s tep
5-30
13th s tep
5-29
12th step
5-28
11t h s tep
5-27
10th step
5-26
9th step
5-25
8th step
5-24
7th step
5-23
6th step
5-22
5th step
5-21
4thstep
5-20
3rd step
5-19
2nd step
5-18
1st step
5-17
Timing Diagram for the Door Close