2

 

Storage and Installations 

Storage: 

The AC drive should be kept in the shipping carton before installation. In order to retain the warranty 
coverage, the AC drive should be stored properly when it is not to be used for an extended period of time. 

Ambient Conditions:   

 

Operation 

 

Air Temperature:

Atmosphere pressure:

Installation Site Altitude:

Vibration:

-10

o

 C to +40

o

 C (14

o

 F to 122

o

 F) 

86 to 106 kPa 
below 1000m 
Maximum 9.86 m/s

2

 (1G) at less than 20Hz 

Maximum 5.88 m/s

2

 (1G) at 20Hz to 50Hz

 

 

Storage

 

Temperature:

Relative Humidity:

Atmosphere pressure:

 
-20

o

 C to + 60

o

 C (-4

o

 F to 140

o

 F) 

Less than 90%, no condensation allowed 
86 to 106 kPa

 

 
Transportation

 

Temperature:

Relative Humidity:

Atmosphere pressure:

Vibration:

-20

o

 C to +60

o

 C (-4

o

 F to 140

o

 F) 

 
Less than 90%, no condensation allowed 
86 to 106 kPa 
Maximum 9.86 m/s

2

 (1G) at less than 20Hz 

Maximum 5.88 m/s

2

 (1G) at 20Hz to 50Hz

 

 

Installations and Connection: 

 

CAUTION 

The control, power supply and motor leads must be laid separately. They must not be fed 
through the same cable conduit / trucking. 
High voltage insulation test equipment must not be used on cables connected to the drive. 
Wait five minutes for DC bus capacitors discharge.

 

 

Any Electrical or mechanical modification to this equipment without prior written 

consent of Delta Electronics, Inc. will void all warranties and may result in a safety 

hazard in addition to voiding the UL listing. 

 

Short Circuit Withstand:

 

Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetrical amperes, for 230V 
Models, the maximum is 240 Volts. 
Improper installation of the AC drive will greatly reduce its life. Be sure to observe the following 
precautions when selecting a mounting location. 

Failure to observe these precautions may void the 

warranty!  

 

 

Do not mount the AC drive near heat-radiating elements or in direct sunlight.   

 

Do not install the AC drive in a place subjected to high temperature, high humidity, excessive 

vibration, corrosive gases or liquids, or airborne dust or metallic particles. 

 

Mount the AC drive vertically and do not restrict the airflow to the heat sink fins. 

 

The AC drive generates heat. Allow sufficient space around the unit for heat dissipation as 

shown in the figure shown next page:

Summary of Contents for VFD-L

Page 1: ...IWAN TEL 886 3 362 6301 FAX 886 3 362 7267 http www deltaww com acdrives NORTH SOUTH AMERICA DELTA PRODUCTS CORPORATION Sales Office P O BOX 12173 5101 DAVIS DRIVE RTP NC 27709 U S A TEL 1 919 767 381...

Page 2: ...001L21A INPUT 1PH 200 240V 50 60Hz 1 4A OUTPUT 3PH 0 240V 0 8A 303VA 100W Freq Range 1 00 120 00Hz DELTA ELECTRONICS INC MADE IN XXXXXX 001L21AT001007 AC Drive Model Input Spec Output Spec Output Freq...

Page 3: ...e conduit trucking High voltage insulation test equipment must not be used on cables connected to the drive Wait five minutes for DC bus capacitors discharge Any Electrical or mechanical modification...

Page 4: ...must connect wiring according to the following circuit diagram shown below L L1 N L2 U T1 V T2 W T3 IM RS 485 Serial Interface 1 EV 2 GND 3 SG 4 SG PIN 1 2 are the power source for the digital keypad...

Page 5: ...starts operation when closes M1 FWD REV Normally Open contact AC drive starts reverse motion when closes MO1 Fault Indication When error is detected MO1 will close RS 485 Serial Communication Port Whe...

Page 6: ...ON 1 2 3 4 5 6 7 Reverse disable ON 1 2 3 4 5 6 7 Low torque output 4 Torque Setting ON 1 2 3 4 5 6 7 High torque output ON 1 2 3 4 5 6 7 Applicable for 40 100W motor 5 Electronic Thermal Setting ON...

Page 7: ...Switch pins 1 to 6 Refer to the description of setting up address VFD L type Communication agreement Modbus ASCII mode protocol 7 N 2 Baud rate 9600 The computer then controls each AC Drive according...

Page 8: ...s n 25 maximum of 50 ASCII codes LRC CHK 1 LRC CHK 0 LRC check sum 8 bit check sum consists of 2 ASCII codes END 1 End characters END1 CR 0DH END0 LF 0AH END 0 ADR Communication Address Valid communic...

Page 9: ...CHK 0 1 CR CR CR CR END 1 END 0 LF END 1 END 0 LF END 1 END 0 LF END 1 END 0 LF CHK check sum LRC Longitudinal Redundancy Check is calculated by summing up the values of the bytes from ADR1 to last da...

Page 10: ...e 1 Low Torque 1 Read Write 7 Electronic Thermal 0 25 60 w 1 40 100 w 1 Read Write 8 Communication Addresses 01 to 63 1 Read Write 9 Software Version Read only Read Only Address List The contents of a...

Page 11: ...ure cF3 3 26 Hardware failure cF3 5 current detection 30 Hardware failure hpf 2 31 Hardware failure hpf 3 Bit 0 to 1 00 STOP 01 Ramp stop 10 Zero speed 11 Operation Bit 2 Reserved Bit 3 to 4 00 Forwar...

Page 12: ...dition that caused the exception is returned An example of exception response of command code 06H and exception code 02H STX 3AH 0 30H ADDRESS 1 ADDRESS 0 1 31H FUNCTION CMD 1 8 38H FUNCTION CMD 0 6 3...

Page 13: ...Voltmeter Periodic Maintenance It is necessary to stop the motor operation during the check up 1 Tighten and reinforce the screws of the AC drive if necessary cause it may loose due to the vibration o...

Page 14: ...nds Over voltage The AC drive detects that the DC BUS voltage has exceeded its maximum allowable value 1 Check whether the input voltage falls within the rated AC Drive input voltage 2 Check for possi...

Page 15: ...Systems SVPWM Space Vector Pulse Width Modulation carrier frequency 10kHz Torque Setting High Low Switching Overload Endurance 150 of rated current for 1 minute Accel Decel Time 0 05 to 30 0 seconds C...

Page 16: ...VFD001L21A VFD40WL11A VFD40WL21A W T3 N L2 V T2 U T1 L L1 Unit mm inch 145 1 5 71 2 7 0 11 8 0 0 31 VFD001L11B VFD001L21B 52 5 2 07 VFD40WL11B VFD40WL21B 155 7 6 13 60 0 2 36 H ig h S T O P F W D 100...

Reviews: