4
Main Circuit Terminals: wire gauge 22-14AWG, torque 10kgf-cm (8.7 in-lbf)
Terminal Symbols
Terminal Functions
L/L1, N/L2
AC line input terminals
U/T1, V/T2, W/T3
Motor connections
Earth Ground
Control Circuit Wiring: wire gauge 22-14AWG, torque 10kgf-cm (8.7 in-lbf)
Terminal
symbols
Terminal names
Remarks
M0 RUN/STOP
Normally Open contact, AC drive starts
operation when closes.
M1 FWD/REV
Normally Open contact, AC drive starts
reverse motion when closes.
MO1
Fault Indication
When error is detected, MO1 will close.
RS-485
Serial Communication
Port
When DIP Switch 7 is ON, the drive is
controlled by RS-485.
DCM
Digital Signal Common
Ground for M0, M1 and M01
Front Panel Control Diagram
GREEN POWER LED
RED ERROR LED
(Please refer to
troubleshooting & Fault
Information)
0.05
5
10
30
5
Accel/Decel Time(Sec)
Unit
Accel/Decel Time Knob (sec.)
0 1
10
100
Output frequency (%)
9
Unit
Output Frequency Knob (Hz)