60
Fault Name Fault Descriptions
Corrective Actions
AC drive E
2
PROM contains
invalid data or can not be
programmed.
Check the connections between the main
control board and the power board.
Reset drive to factory defaults.
Ground fault or fuse failure:
Ground fault :
The AC drive output is
abnormal. When the output
terminal is grounded (short
circuit current is 50% more
than the AC drive rated
current), the AC drive power
module may be damaged.
The short circuit protection is
provided for the AC drive
protection, not user
protection.
Ground fault :
1. Check whether the IGBT power module is
damaged.
2. Check for possible poor insulation at the
output line.
Fuse failure:
The fuse failure information
will be displayed by the LED
located on the power board.
Fuse failure:
1. Replace Fuse.
2. Check whether the IGBT power module is
damaged.
3. Check for possible poor insulation at the
output line.
External baseblock.
AC drive output is turned off.
When the multi-function input 1 (2, 3)-DCM
terminal goes from OFF to ON, the AC drive
output will be turned off.
Drive’s internal circuitry
abnormal.
Switch off power supply. Check whether the
input voltage falls within the rated AC drive
input voltage. Switch on the AC drive.
Protection circuitry of
hardware detected abnormal
operation.
Remove power from the AC drive and then
restore power. If H.P.F. fault appears again, the
AC drive should be returned for service.
Summary of Contents for VFD-A
Page 1: ......
Page 2: ...5011200503 200305 22 AE02...
Page 3: ......
Page 65: ...61 APPENDIX A Standard Specifications...
Page 77: ...73 Remote Controller RC01 Adapter Unit mm inches Standard Extension Cable Unit mm...
Page 79: ...75 Braking Resistors Braking Units Braking Resistors Braking Units...
Page 80: ...76 Braking resistors model no BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040...