46
Display Functions
Pr.64
Function Display Setting
Parameter #
64
Parameter Name
Displays the contents of the monitored item
Factory Setting
d0000
Settings
d0000 Displays the actual operating frequency (H)
d0001 Displays the user-defined setting (v)
d0002 Displays the value of the internal counter (c)
Displays the contents of the monitored item as follows:
H: Displays the actual operation frequency
v: Displays the user-defined setting ( where v = H x Pr.65 )
c: Displays the value of the internal counter. This counter is triggered by an
external signal provided via the external input TRG. When the counter reaches
d0000 during count down, the multi-function output terminal MO1 or MO2 will be
“closed” (Refer to Pr.45, 46). The counter will use the value contained in Pr.66 as
its starting point when another count down is to be executed.
Pr.65
Coefficient K Setting
Parameter #
65
Parameter Name
Coefficient of line speed
Factory Setting
d001.0
Units
0.1
Parameter value
d000.1 - d200.0
This parameter can be programmed while the drive is running.
Coefficient K determines the multiplying factor for the user-defined setting (v).
The value of the user-defined setting (v) is calculated and displayed as follows:
Display value of v = output frequency x K. The maximum value that can be
displayed is
. If the value of v exceeds 9999, the actual value is equal to
the display value multiplied by 10.
Summary of Contents for VFD-A
Page 1: ......
Page 2: ...5011200503 200305 22 AE02...
Page 3: ......
Page 65: ...61 APPENDIX A Standard Specifications...
Page 77: ...73 Remote Controller RC01 Adapter Unit mm inches Standard Extension Cable Unit mm...
Page 79: ...75 Braking Resistors Braking Units Braking Resistors Braking Units...
Page 80: ...76 Braking resistors model no BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040...