9
Control Circuit Wiring
(1) Control terminal block designations
The control leads must be routed separately from the power supply and motor leads.
They must not be fed through the same cable conduit.
Terminal Symbol
220V/440V Class 1
∼
5HP (AWG: 28 – 14; Torque:4 kgf-cm)
RA
ACI
AVI
+10V
RB
RC
MO1
ACM
AFM
MCM
MO2
MI1
RST
REV
FWD
MI2
MI3
DCM
TRG
EF
SG-
SG+
DFM
DCM
+EV
220V/440V Class 7.5
∼
30HP (AWG: 24 – 12; Torque:4 kgf-cm)
RA
ACI
AVI
+10V
RB RC
MO1
ACM
AFM
MCM
XX
MO2
MI1
RST
REV FWD
MI2 MI3
DCM
TRG
EF
SG
SG+
DFM
(2) Control terminal block descriptions
Close Contacts
between Terminals
Terminals Use
Function
RA - RC
Multi-function indication output
contact
Refer to Chapter 5, Pr.57
RB - RC
Multi-function indication output
contact
MI1 - DCM
Multi-function input 1
MI2 - DCM
Multi-function input 2
Refer to Chapter 5, Pr.39, 40, 41
MI3 - DCM
Multi-function input 3
REV - DCM
Reverse / Stop
“Open”
→
stop, “Close”
→
Reverse
FWD - DCM
Forward / Stop
“Open”
→
stop, “Close”
→
Forward
RST - DCM
Reset
“Close”
→
Reset
EF - DCM
External fault
“Close”
→
External fault
DFM - DCM
Digital frequency meter
Digital frequency output (0, +10 V)
TRG - DCM
Counter trigger input
“Open”
→
“Close”:(counter value)+1
MO1 - MCM
Multi-function PHC output 1
Refer to Pr.45, 46
MO2 - MCM
Multi-function PHC output 2
(open collector output)
+10V - ACM
Power supply for speed setting +10 V (20 mA max. output current)
AVI - ACM
Analog voltage input
0
∼
10 V (Max. output freq.) input
ACI - ACM
Analog current input
4
∼
20 mA (Max. output freq.) input
AFM - ACM
Analog frequency/current
meter
0
∼
10 V (Max. output freq.) output
SG+ - SG-
Serial communication interface RS-485 serial port
+EV - DCM
Auxiliary control power source DC 20V ~ 24V (50mA Max.)
Note:
Use twisted-shielded or twisted-pair shielded-lead wires for the control signal. It is
recommended to run signal wiring in a separate steel conduit. The shield wire should only be
connected at the drive.
Summary of Contents for VFD-A
Page 1: ......
Page 2: ...5011200503 200305 22 AE02...
Page 3: ......
Page 65: ...61 APPENDIX A Standard Specifications...
Page 77: ...73 Remote Controller RC01 Adapter Unit mm inches Standard Extension Cable Unit mm...
Page 79: ...75 Braking Resistors Braking Units Braking Resistors Braking Units...
Page 80: ...76 Braking resistors model no BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040...