Ultron HPH Integrated Battery Series
UPS
Suggested Protective Device
Suggested Supplier
20kVA
D-Curve 63A circuit breaker
Input & Bypass: CHNT (CB-60D)
30/ 40kVA D-Curve 125A circuit breaker
Input & Bypass: CHNT (CB-125 D125)
y
When connecting the UPS to the critical loads, you must install a 3-pole EN 60947-2 certi-
> * >
UPS
Suggested 3-pole Breaker
Suggested Supplier
20KVA
C-Curve 63A Breaker
Output: CHNT (CB-60 C63)
30KVA
C-Curve 63A Breaker
Output: CHNT (CB-60 C63)
40KVA
C-Curve 100A Breaker
Output: CHNT (CB-125 C 100)
y
Check that the size, diameter, phase, and polarity of each cable that needs connecting
'* : !
please refer to
Table 6-1
.
!"
Capacity (kVA)
20kVA
30kVA
40kVA
AC Input cable
8AWG/ 6mm²
6AWG/ 10mm²
4AWG/ 16mm²
Output cable
8AWG/ 6mm²
6AWG/ 10mm²
4AWG/ 16mm²
Battery Input cable
6AWG/ 10mm²
4AWG/ 16mm²
2AWG/ 25mm²
Tightening Torque
20.4 Kgf.cm
61.2 kgf.cm
61.2 kgf.cm
Input Breaker
63A (4-pole×1)
63A (4-pole×1)
100A (4-pole×1)
Bypass Breaker
63A (4-pole×1)
63A (4-pole×1)
100A (4-pole×1)
NOTE:
1. In accordance with
National Electrical Codes (NEC)
, please install a suitable
conduit and bushing.
2. Please refer to national and local electrical codes for acceptable non-fuse
breakers and cable size.
3. Cables with PVC material and with temperature resistance up to 105°C are
suggested.
4. Make sure that the input/ output cables are locked tightly.