Quick Installation Guide for Solar Power Inverter M88H EU V3 EN 5013240202 02 2018-03-22
Commissioning – basic settings
To make the settings as described in this chapter, the inverter must be powered with alternating current (mains grid).
The inverter also needs a DC voltage in order to operate fully from the energy provider.
Français
Deutsch
English
Select language
1.
Use the
and
buttons to select the
English
language and then press the
ENT
button.
FRA-Is 60HZ
UK G59-3 230
FRA-Is 50HZ
FRA-Is 60HZ
FRANCE MV
2.
Use the
and
buttons to select your country or mains type and then press
the
ENT
button.
Yes / No
UK G59-3 230
set country:
Are you sure to
3.
Check that the correct country or mains type is selected.
If the correct country is selected, use the
and
buttons to select the
Yes
entry and the press the
ENT
button.
To change the selection, press the
EXIT
button.
SUNSPEC prot.
Delta prot.
NOTICE
The Delta protocol is the Delta Modbus protocol and is intended for utilization with the
Delta Service Software.
4.
Use the
and
buttons to select SUNSPEC as RS485 protocol option and
then press the
ENT
button.
Yes / No
SUNSPEC prot.
set protocoll:
Are you sure to
5.
Check that the correct protocol is selected.
If the protocol is selected, use the
and
buttons to select the
Yes
entry and
then press the
ENT
button.
Press the
EXIT
button to change the selection
ID=001
Setting ID:
NOTICE
If multiple inverters are connected to the PV system then a different inverter ID must set for
each inverter. For example, the inverter ID is used by monitoring systems to uniquely iden-
tify each inverter.
6.
Use the
and
buttons to set the individual digits and then press the
ENT
button.
Yes / No
ID: 1
Are you sure to set
7.
Check that the correct inverter ID is set.
If the correct inverter ID is selected, use the
and
buttons to select the
Yes
entry and the press the
ENT
button.
Press the
EXIT
button to change the selection
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Feb 2017 15:32
þ
The basic settings are now complete. The standard menu is displayed.
→ The inverter starts a self-test lasting approx. 2 minutes. The remaining time is
shown on the display.