55
Quick Installation Guide for Solar Power Inverter M88H EU V3 EN 5013240202 02 2018-03-22
Mechanical details
M88H_121 (ST)
Dimensions (W x H x D)
960 × 615 × 275 mm
Weight
84 kg (power module: 68 kg)
Cooling
3 fans
AC connection type
Phoenix Contact UKH 150
DC connection type
Phoenix Contact UKH 150
Communication interfaces
2x RS485, 2x dry contacts, 1x external power-off, 6x digital inputs
General specifications
M88H_121 (ST)
Delta model name
RPI M88H_121
Delta part number
RPI883M121200
Maximum efficiency
98.8%
EU efficiency
98.5%
Operating temperature range
-25 ... +60 °C
Operating temperature range without derating
-25 ... +40 °C
Storage temperature range
-25 ... +60 °C
Relative humidity
0 ... 100%, non-condensing
Max. operating height
3000 m above sea level
Noise level (at a distance of 1 m)
75.8 dB(A)
Standards and guidelines
M88H_121 (ST)
Protection degree
IP65
Safety class
I
Pollution degree
II
Overload behavior
Current limit, power limit
Safety
IEC 62109-1 / -2, CE-compliance
EMC
EN 61000-6-2, EN 61000-6-3
Fault-free operation
IEC 61000-4-2 / -3 / -4 / -5 / -6 / -8
Harmonic distortion
EN 61000-3-2
Fluctuations and fibrillations
EN 61000-3-3
Mains connection guidelines
You will find the current list at www.solar-inverter.com.
1)
IEC 60664-1, IEC 62109-1
2)
The specified value applies for a temperature of 25 °C in the interior of the inverter. At higher temperatures, the value can drop down to 10 A.
3)
EN 50539-11
4)
For cos phi = 1 (VA = W)
5)
Can occur under the following conditions: DC input voltage > 540 V; symmetrical design; ambient temperature < 35 °C.
6)
Can occur under the following conditions: DC input voltage > 650 V; symmetrical design; ambient temperature < 35 °C.
7)
AC voltage and frequency range are programmed using the corresponding country specifications.
8)
EN 61463-11
Technical Data – M88H_121 (ST)