Quick Installation Guide for Solar Power Inverter M50A_12s EU V4 EN 2018-10-24
Dry contacts
E-Today: 0kWh
Power: 0W
Status: On Grid
12.Jun 2016 16:02
1.
If the default information is displayed, press the
EXIT
button to open the main menu
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Install Settings
entry and then press
the
ENT
button
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555
Use the
and
buttons to set the individual numerals
Press the
ENT
button to confirm a numeral.
Grid Settings
DC Injection
Dry Cont.
RCMU: ON
EPO: Normal Open
4.
Use the buttons
and
to select the
Dry Cont.
entry and press the
ENT
button
Dry Cont.B Disable
Dry Cont.A Disable
5.
Use the buttons
and
to select a dry contact and press the
ENT
button The
current setting is shown after the name of the dry contact
On Grid
Fan Fail
Insulation
Disable
6.
Use the
and
buttons to select an option and then press the
ENT
button
See “Connecting digital inputs, external shutdown and dry contacts (optional)”, page 20
for the available options
Commissioning – further settings (optional)