4 5
Ultron HPH Series UPS
Model
HPH-20K-LV-B
HPH-20K-LV-
BN*
1
HPH-30K-LV-B
HPH-30K-LV-
BN*
1
HPH-40K-LV-B
HPH-40K-LV-
BN*
1
HPH-60K-LV-B
HPH-60K-LV-
BN*
1
Audible Noise
< 65 dBA
< 70 dBA
LED & LCD
LED indicators and Multi-language LCD display
Communication Interfaces
SMART Slot × 1, MINI Slot × 1, Parallel Port × 2, RS232 Port × 1,
REPO Port × 1, Charger Detection Port × 1, Input Dry Contact × 2,
Output Dry Contact × 6
Environ-
ment
Operating
Altitude
3280 ft (without derating)
1000 meters (without derating)
Operating
Temperature
32 ~ 104°F (0 ~ 40°C)
Ambient
Storage
Temperature
5 ~ 104°F (-15 ~ 40°C)
Relative
Humidity
0 ~ 95% (non-condensing)
Physical
Dimensions
(W x D x H)
20.5" × 31.5" × 54.3"
(520 × 800 × 1380 mm)
20.5" × 31.5" × 69.3"
(520 × 800 × 1760 mm)
Weight
(with batt.)
749.6 lb
(340 kg)
925.9 lb
(420 kg)
992.1 lb
(450 kg)
1168.4 lb
(530 kg)
Weight
(without batt.)
432.1 lb
(196 kg)
449.7 lb
(204 kg)
515.9 lb
(234 kg)
533.5 lb
(242 kg)
NOTE:
1. Refer to the rating label for the safety rating.
$OOVSHFL¿FDWLRQVDUHVXEMHFWWRFKDQJHZLWKRXWSULRUQRWLFH
3. *
1
: UPS with this model has no batteries inside.
4. *
2
: When input voltage range is 72 ~ 108Vac (L-N) and 125 ~ 187Vac (L-L), the sustainable
loading is from 63% to 100% of UPS capacity.
5. *
3