Ultron HPH Series UPS
1.4 Storage
Warnings
y
Prior to Installation
If the UPS needs to be stored prior to installation, it should be placed in a dry area. The
allowable storage temperature is between 5°F (-15°C) and 104°F (40°C).
y
After Usage
Press the
OFF
key (
OFF
) once and the LCD will appear with the following screen. If you
want to turn off the UPS, please press the
DOWN
key (
). Make sure the UPS is in
bypass mode, disconnect the UPS from the utility power and the battery power, remove
all equipment from the UPS and store the UPS in a dry and well-ventilated area at a
temperature between 5°F (-15°C) and 104°F (40°C). Idle batteries must be fully recharged
approximately every three months if the UPS needs to be stored for an extended period
of time. The charging time must not be less than 24 hours each time.
?