Ultron HPH Series UPS

y

 Dual Input (Single Unit)

When there are two AC power sources, single unit wiring procedures are as follows.

1

 Follow 

5.5.2 Single Input/ Dual Input Modification

 to modify the UPS into dual 

input. Please note that only authorized Delta engineers or service personnel can 
modify single input/ dual input setup.

2

 Follow 

steps 

1

 ~ 

5

 stated in section 

Single Input (Single Unit)

.

3

  Connect the main AC source/ bypass source/ output/ external battery cabinet cables 

to the relevant wiring terminal blocks and do not forget to ground the UPS (please 
refer to 

Figure 5-12 

and

 

Figure 5-13

).

(Figure 5-12: Single Unit Dual Input Wiring Diagram_20/ 30kVA)

1 2 3 4

E X T . S W I T C H

S T A T U S

BATTERY INPUT

144V DC

144V DC

Front View - 20/ 30kVA

Rear View - 20/ 30kVA

For the UPS

grounding 

For the 
critical loads’ 
grounding 

External Manual 
Bypass Breaker 
and Output Breaker
ON/ OFF Detection

R S T 

N

R S T 

N

R S T

N

R S T 

N

Connects the

main AC source

Connects the

bypass source

Connects the

critical loads

Bypass
Breaker

Input

Breaker

Manual
Bypass
Breaker

Connects the external 

battery cabinet

For the external 
battery cabinet’s

grounding 

-

+

N

Output
Breaker

Summary of Contents for HPH-20K-LV-B

Page 1: ...Family The power behind competitiveness www deltapowersolutions com HPH Series Three Phase 20 30 40 60 kVA 208V User Manual EPO ON OFF NORMA L BATTE RY BYPAS S FAULT ESC EPO ON OFF NORMA L BATTE RY B...

Page 2: ...I WKLV SURGXFW Q GLVSRVLWLRQ GXSOLFDWLRQ GLVVHPLQDWLRQ UHSURGXFWLRQ PRGL FDWLRQ WUDQVODWLRQ extraction or usage of this Manual in whole or in part is prohibited without the prior written permission of...

Page 3: ...l Panel 8 3 4 Front View with Door Open and Internal Panel Removal 9 3 5 Rear View 15 Chapter 4 Operation Modes 17 Chapter 5 Installation and Wiring 22 5 1 Precautions Prior to Installation and Wiring...

Page 4: ...LRQ WHFKQRORJ HTXLSPHQW DQG XVHG WR SRZHU computers servers and associated peripheral devices If you want to connect any capac itive loads or non linear loads that have serious surge current to the UP...

Page 5: ...HG E TXDOL HG VHUYLFH SHUVRQQHO y Do not open or mutilate the battery or batteries The released electrolyte is harmful to the skin and eyes and may be toxic y R QRW GLVSRVH RI WKH EDWWHU RU EDWWHULHV...

Page 6: ...he UPS and store the UPS in a dry and well ventilated area at a temperature between 5 F 15 C and 104 F 40 C Idle batteries must be fully recharged approximately every three months if the UPS needs to...

Page 7: ...al line Battery neutral line 16 For UPS grounding 17 For critical load grounding For external battery cabinet grounding 18 Positive battery terminal 19 Negative battery terminal 1 6 Standard Complianc...

Page 8: ...sign of DSP digital control technology DQG KLJKHVW TXDOLW DVVHPEO ZLWK DQ RXWSXW SRZHU IDFWRU XS WR XQLW 7KH HI FLHQF RI WKH UPS reachs up to 94 in online mode and up to 98 in ECO mode With its outsta...

Page 9: ...ce and Dimensions Figure 3 1 20 30kVA UPS Appearance and Dimensions Figure 3 2 40 60kVA UPS Appearance and Dimensions EPO ON OFF NORMA L BATTER Y BYPAS S FAULT ESC 54 3 1380 mm 31 5 800 mm 20 5 520 mm...

Page 10: ...ED Indicators Door Handle No Item Description 1 LCD Display Control Panel and LED Indicators 1 LCD displays the status of the UPS RQWURO SDQHO LQFOXGHV 6 PRYH XS PRYH GRZQ FRQ UPDWLRQ ON OFF and EPO b...

Page 11: ...e batteries are discharging 3 BYPASS The UPS is operating in bypass mode 4 FAULT The UPS has abnormalities 5 LCD Display Displays the UPS operating status and relevant monitoring data 6 ON ON key Pres...

Page 12: ...he EPO key EPO press the unit s OFF key OFF for 3 seconds and then press the unit s ON key ON for 3 seconds to enter into online mode 3 4 Front View with Door Open and Internal Panel Removal y Models...

Page 13: ...al Battery Cabinet The four UPS models have different contents inside the internal battery cabinet Please refer to the table below for more information 1 The internal battery cabinet includes No Item...

Page 14: ...3 4 Connect to the user supplied Output Breaker NOTE The Manual Bypass Breaker and Output Breaker should be supplied by the user and connected to the above mentioned External Switch Status Dry Contact...

Page 15: ...ypass Input Terminal Block N R S T Connects to the bypass source 3 UPS Output Terminal Block N R S T Connects to the critical loads 4 For the UPS grounding 5 For the critical loads grounding y Models...

Page 16: ...XT SWITCH STATUS EXT SWITCH STATUS 20kVA 30kVA 2 1 2 1 3 4 3 4 1 2 3 4 1 2 3 4 EXT SWITCH STATUS EXT SWITCH STATUS 40kVA 60kVA 2 1 2 1 3 4 3 4 Figure 3 10 Front View with Door Open and Internal Panel...

Page 17: ...JXUDWLRQ SOHDVH UHIHU to Figure 3 6 and 5 5 3 Single Unit Wiring 7 Only service personnel can perform battery installation wiring and connection 3 External Switch Status Dry Contacts Figure 3 11 Exte...

Page 18: ...SLOT PARALLEL PARALLEL PARALLEL SWITCH EXT BATTERY CHARGER DETECTION INPUT DRY CONTACT OUTPUT DRY CONTACT REPO RS 232 BATTERY INPUT 144V DC 144V DC 20 30kVA 40 60kVA 1 2 3 4 5 6 7 8 9 10 11 12 13 14...

Page 19: ...y event occurs the UPS immediately disconnects the power supply and shuts down the unit safely 12 Charger Detection Port Connects to a charger box and detects the charger status 13 Battery Input Termi...

Page 20: ...ne Mode The critical load is supplied by the inverter which derives its power from the utility AC power and the UPS charges the batteries as needed and provides power protection to the equipment Durin...

Page 21: ...ectrical Power through the UPS in Standby Mode y ECO Mode The UPS can be set in ECO mode manually In ECO mode when the utility input voltage is within the 10 range of rated voltage the load is supplie...

Page 22: ...PA MAIN LOAD Batteries Rectifier Inverter Figure 4 4 Path of Electrical Power through the UPS in Battery Mode Table 4 1 The battery status is as follows Battery Capacity Buzzer LCD Display Full Mid Th...

Page 23: ...wer through the UPS in Bypass Mode y Manual Bypass Mode If UPS system maintenance or repair is required the UPS system may be bypassed without interrupting the supply of power to the attached load WAR...

Page 24: ...After the output frequency is set up the system will automatically disable the bypass function Once the inverter shuts down there is no bypass output During converter mode the NORMAL LED indicator NO...

Page 25: ...binets and all handling equipment For the weight of the UPS please refer to SSHQGL 7HFKQLFDO 6SHFL FDWLRQV y The installation place must be kept clean and tidy at all times y Ensure that the installat...

Page 26: ...nce 5 4 UPS Installation To avoid tipping the UPS please reinstall the balance supports that were removed from the UPS during the unpacking process Please follow the following steps 1 After you decide...

Page 27: ...TTE RY BYPAS S FAULT ESC Balance Support x 4 M8 Screw x 8 3 Use eight user supplied M10 bolts to fix the four balance supports on the ground to avoid UPS movement Figure 5 3 Fix the Balance Supports o...

Page 28: ...uggested protective devices For the installation of the protective devices and 4 pole contactors please see Figure 5 9 5 10 5 12 and 5 13 UPS Suggested Protective Device 20kVA D Curve 75A circuit brea...

Page 29: ...eptable non fuse breakers and cable size 3 Cables with PVC material and with temperature resistance up to 221 F 105 C are suggested 4 Make sure that the input output battery cables are locked tightly...

Page 30: ...ground terminal of the UPS must be grounded Please use ring type terminal for wiring WARNING 1 Incorrect wiring will lead to severe electric shock and damage to the UPS 2 For single input the UPS will...

Page 31: ...T Connects to the bypass source 3 UPS Output Terminal Block N R S T Connects to the critical loads 4 For the UPS grounding 5 For the critical loads grounding 2 Remove the three cables shown in Figure...

Page 32: ...Single Unit When there is only one AC power source single unit wiring procedures are as follows 1 Open the UPS s front door remove the front and rear panels and you will see the wiring terminal block...

Page 33: ...Front View_Wring Terminal Block_40 60kVA 40 60kVA T S R N T S R N T S R N 1 2 3 4 5 Rear View BATTERY INPUT 144V DC 144V DC BATTERY INPUT 144V DC 144V DC 40 60kVA Model 20 30kVA Model 7 6 7 6 Figure 5...

Page 34: ...nel to see the Battery Input Terminal Block Connects an external battery cabinet Only batteries with the same type and rating can be paralleled 7 For the external battery cabinet s grounding 3 RQ UP W...

Page 35: ...144V DC Rear View 20 30kVA R S T N For the UPS grounding For the critical loads grounding Connects the main AC source Connects the critical loads Output Breaker Input Breaker Manual Bypass Breaker Con...

Page 36: ...unding R S T N R S T N N External Manual Bypass Breaker and Output Breaker ON OFF Detection 7 2QO TXDOL HG VHUYLFH SHUVRQQHO FDQ SHUIRUP LQWHUQDO EDWWHU LQVWDOODWLRQ DQG ZLULQJ For UPS with part No GE...

Page 37: ...eries should be installed UPS 20kVA 30kVA 40K kVA 60K kVA String Q ty 2 3 3 4 Battery Q ty 48 72 72 96 NOTE One string includes 24 batteries Figure 5 11 Internal Battery Installation and Wiring 40kVA...

Page 38: ...ables to the relevant wiring terminal blocks and do not forget to ground the UPS please refer to Figure 5 12 and Figure 5 13 Figure 5 12 Single Unit Dual Input Wiring Diagram_20 30kVA 1 2 3 4 EXT SWIT...

Page 39: ...T N Connects the main AC source Connects the bypass source Connects the critical loads Bypass Breaker Input Breaker Manual Bypass Breaker Output Breaker Connects the external battery cabinet For the e...

Page 40: ...es to the relevant wiring terminal blocks and do not forget to ground the parallel UPSs please refer to Figure 5 9 5 10 and Figure 5 14 UPS 1 UPS 2 UPS 4 I P LOAD AC Input AC Input AC Input UPS Output...

Page 41: ...that the parallel UPSs can equally share the equipment loads in bypass mode 2 Only UPSs with the same capacity voltage and frequency can be paralleled otherwise parallel functions will fail HIRUH VWDU...

Page 42: ...5 Set up each UPS s parallel switch in the ON or OFF position NOTE When you parallel UPSs you need to set up each UPS s parallel switch to activate parallel function The parallel switch includes two D...

Page 43: ...5 6 External Battery Cabinet Connection Precautions WARNING 1 You can connect loads to the UPS only after the batteries are fully charged 7KLV JXDUDQWHHV WKDW WKH 836 FDQ SURYLGH VXI FLHQW EDFNXS SRZ...

Page 44: ...bat 123V PF 0 9 1 Vbat 120V PF 1 0 9 RU LQWHUQDO EDWWHU FRQ JXUDWLRQ RQH VWULQJ LQFOXGHV EDWWHULHV I RX would like to use the internal batteries and the external batteries at the same time please make...

Page 45: ...pole 300Vdc and 3 pole 450Vdc Follow Figure 5 16 to install a 3 pole non fuse DC breaker and fast acting fuses between the UPS and the external battery cabinet Figure 5 16 A 3 pole Non fuse DC Breaker...

Page 46: ...A 208V Series UPS uses sealed lead acid batteries The battery life depends on the temperature the usage and the charging discharging frequency High temperature environments and high charging dischargi...

Page 47: ...40 70 Hz Input Current 67 5A 100A 135A 200A Power Factor 0 99 full load Output Voltage 208 120Vac 220 127Vac Power Factor Unity Voltage Regulation 1 Voltage Harmonic Distortion 1 5 linear load Overloa...

Page 48: ...rature 32 104 F 0 40 C Ambient Storage Temperature 5 104 F 15 40 C Relative Humidity 0 95 non condensing Physical Dimensions W x D x H 20 5 31 5 54 3 520 800 1380 mm 20 5 31 5 69 3 520 800 1760 mm Wei...

Page 49: ...sistible force i e war fire natural disaster etc and this warranty also expressly excludes all incidental and consequential damages Maintenance service for a fee is provided for any damage out of the...

Page 50: ......

Page 51: ...w com Delta Electronics Korea Inc 1511 Byucksan Digital Valley 6 cha Gasan dong Geumcheon gu Seoul Korea 153 704 T 82 2 515 5303 E ups south korea deltaww com Delta Electronics Int l Singapore Pte Ltd...

Page 52: ......

Reviews: