4.8.2 Digital Input
To implementation of power management, the digital input interface receives the
specifications of the network operator via a ripple control receiver.
• Australia and New Zealand:
• Customer :
User defined.
The inverter can detect the state of the relay of the ripple control receiver.
The information which relay shall be controlled parameter by the network operator.
The inverter support the demand response mode (DRMs).
DRM 0 - Operate the disconnection device.
DRM 1 - Do not consume power
DRM 2 - Do not consume at more than 50% of rated power
DRM 3 - Do not consume at more than 75% of rated power and source reactive power
DRM 4 - Increase power consumption
(subject to constraints from other active DRMs)
DRM 5 - Do not generate power.
DRM 6 - Do not generate at more than 50% of rated power.
DRM 7 - Do not generate at more than 75% of rated power and sink reactive power.
DRM 8 - Increase power generation.
(subject to constraints from other active DRMs)
4.8.1 Installation of the Rubber Washer
(1) Loosen the front cover
①
counterclockwise.
(2) Remove the rubber washer
②
from the fastening ring
③
.
(3) Remove the washer plugs
④
and insert the cable from the cut out of rubber
washer
②
.
(4) Connect the cable with the terminal.
(5) Install the rubber washer
②
to the fastening ring
③
.
(6) Surely tighten the front cover
①
.
* To ensure contactment, please make sure cables are not twisted.
①
②
④
③
Φ6.0mm x3
23
Installation and Wiring