Force-GT DIN Rail Power Supply
24 V 960 W 3 Phase / DRF-24V960W3GBA
TECHNICAL DATASHEET
All parameters are specified at 25°C ambient and AC input
3x unless otherwise indicated.
www.DeltaPSU.com (May 2022, Rev. 00)
3
Mechanical
Case Cover / Chassis
Aluminum
Dimensions (H x W x D)
124 x 110 x 128.7 mm (4.88 x 4.33 x 5.07 inch)
Unit Weight
2.26 kg (4.98 lb)
Indicator
Green LED DC OK
Cooling System
Convection
Terminal*
5
Input 4 Pins (Rated 600 V / 30 A)
Output 4 Pins (Rated 300 V / 65 A)
Signal 2 Pins (Rated 300 V / 12 A)
Wire
Input AWG 18-10
Output AWG 12-6
Signal AWG 20-16
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
Noise (1 Meter from power supply)
Sound Pressure Level (SPL) < 25dBA
*5 The torque at the input terminal connector shall not exceed 5.4 Kgf.cm. (4.7 lbf.in). The torque at the output terminal connector shall not exceed 19.7 Kgf.cm. (17.1 lbf.in).
Environment
Surrounding Air Temperature
Operating
3-Phase
-25°C to +70°C (-40°C Cold Start)
2-Phase
-25°C to +60°C (-40°C Cold Start)
Storage -40°C to +85°C
Power De-rating
Vertical Mounting > 55°C de-rate power by 3.33% / °C
Horizontal Mounting > 25°C de-rate power by 2.5% / °C
Input Voltage
2-Phase
2 x 340-575 Vac de-rate power to 80%
Operating Humidity
5 to 95% RH (Non-Condensing)
Operating Altitude and
Over Voltage Category
OVC III 0 to 2,500 Meters (8,200 ft.)
According to IEC/EN 62477-1 /
EN 60204-1 (clearance and
creepage distances) and IEC
62103 (safety part)
OVC II 2,500 to 6,000 Meters
(19,680 ft.)
0 to 5,000 Meters (16,400 ft.) According to IEC/EN 62368-1,
IEC/EN 61010
Shock Test
Non-Operating IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms;
3 times per direction
Vibration
Operating IEC 60068-2-6, Sine Wave: 10-500 Hz; 3G peak;
60 min per axis for all X, Y, Z directions
Pollution Degree
2