Electrical Specifications

 Model 

 Item 

DVPPS01 

DVPPS02 

DVPPS05 

Power input 

100 ~ 240VAC (-15% ~ +10%), 50/60Hz 

Output power 

24VDC (±3%) 

Maximum output current 

1 A 

2 A 

5 A 

Ripple & noise 

Under 100mV

p-p

 Typical at 

full load 

Under 240mV

p-p

 Typical at full load 

Efficiency 

78% ~ 87% Typical at full load 

Above 88% Typical at full load

Overcurrent/short circuit 
protection 

Auto Recovery 

Overvoltage/ 
overtemperature 
protection 

--

Overvoltage protection: The 
power supply is cut off for 5 
seconds. DVPPS05 operates 
normally after power is 
supplied. 
Overtemperature protection: 
The power supply is cut off for
5 seconds, and the 
temperature inside DVPPS05 
falls to the temperature below 
85

o

C. DVPPS05 operates 

normally after power is 
supplied.

Grounding 

The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and 
N (All PLC units should be grounded directly to the ground pole). 

Operation environment 

0°C~55°C (temperature), 50~95% (humidity), Pollution 
degree 2 

-20°C~55°C (temperature), 
50~95% (humidity), 
Pollution degree 2 

Storage environment 

-25°C~70°C (temperature), 5~95% (humidity) 

UL 

UL508 Listed (Industrial Control Equipment) 

Agency 
approvals 

CE 

European Community EMC 
Directive 89/336/EEC and 
Low Voltage Directive 
73/23/EEC 

EMC Directive 2004/108/EC and Low Voltage Directive 
2006/95/EC 

Weight (g) 

158 

250 

488 

Z

Installation and Wiring

ƒ

Mounting Arrangements and Wiring

DIN Rail Installation: 

The DVPPS can be secured to a cabinet by using the DIN rail 
that is 35mm high with a depth of 7.5mm. When mounting the 
DVPPS on the DIN rail, be sure to use the end bracket to stop 
any side-to-side motion of the DVPPS, thus to reduce the 
chance of the wires being pulled loose. On the bottom of the 
DVPPS is a small retaining clip. To secure the DVPPS to the 
DIN rail, place it onto the rail and gently push up on the clip. To 
remove it, pull down on the retaining clip and gently pull the 
DVPPS away from the DIN rail. Please see the figure on the 
right:

For heat dissipation. Make 
sure to provide a minimum 
clearance of 50mm between 
the unit and all sides of the 
cabinet. (as shown below) 

Direct mounting: Tighten M4 screws into direct mount hole. 