background image

Wiring: 

To suit M3.5 screw terminals

Below 6.2

Below 6.2

1.  Please use O-type or Y-type terminals for I/O wiring terminals. The 

specification for the terminals is as shown on the left. Tighten PLC terminal 
screws to a torque of 5 ~ 8kg-cm (4.3 ~ 6.9 in-lbs). 

2.  Please avoid tiny metal material enter DVPPS01/02/05 when screwing and 

wiring. After finishing wire, remove the affix that pasted on the heat sink for 
heat dissipation. 

3.  Use Copper Conductors Only, 60°C. 

ƒ

Wiring Notes

ƒ

Environment 

1.  DO NOT store the DVPPS01/02/05 in a dusty, smoky, or corrosive atmosphere. 
2.  DO NOT store the DVPPS01/02/05 in an environment with high temperature or high humidity. 
3.  DO NOT install PLC on a shelf or on an unstable surface. 

ƒ

Power Input Wiring 

Power input of DVPPS01/02/05 is AC input; following items should be noticed: 

1.  Connect the AC input (100VAC ~ 240VAC) to terminals L and N. Any 110VAC or 220VAC connected to the 

+24V terminal will permanently damage the DVPPS01/02/05. 

2.  Please use wires of 1.6mm and above for the grounding. 
3.  If the power-cut time is less than 10ms, the DVPPS01/02/05 still operates unaffectedly. If the power-cut 

time is too long, the DVPPS01/02/05 will stop operating and all the outputs will be Off. 

[

Trial Run

ƒ

 Power indicator, Running and Test 

The “POWER” LED at the front of DVPPS01/02/05 will be lit (in green) if the power is on. If the indicator is not 
ON, it indicates that the power supply is not enough or short circuit. Please check your power wiring. 

\

Troubleshooting

Judge the errors by the indicators on the front panel. When errors occurred on DVPPS01/02/05, please check: 

ƒ

 “POWER”  LED 

The “POWER” LED at the front of the MPU will be lit (in green) if the power is on. If the indicator is not on 
when the MPU is powered up, please check if power supply is normal. If the indicator is not on when the MPU 
is powered up and with the input power being normal, it is an indication that the PLC is malfunction. Please 
have this machine replaced or have it repaired at a dealer near you. 

Reviews: