- 6 -
E
xample:
1.
Use Pt1000(
H00)
to set CH1, NTC 30K(H06) for CH2;
and
the setting value
would be
H0600
written into
CR#1.
2.
Use Self
-
defined temperature/resistance table
8
(H19) and disable channel for CH6 (HFF); the
s
etting value would be HEF19 written into
CR#3.
Error Code Register(CR#15)
Error Status
Value
b15 ~ b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH1
Invalid measured
value or sensor
connection failure
K1
(
H1
)
Reserved
0 0 0 0 0 0 0 0 0 1
CH
2
Invalid measured
value or sensor
connection failure
K2
(
H2
)
0 0 0 0 0 0 0 0 1 0
CH
3
Invalid measured
value or sensor
connection failure
K4
(
H4
)
0 0 0 0 0 0 0 1 0 0
CH
4
Invalid measured
value or sensor
connection failure
K8
(
H8
)
0 0 0 0 0 0 1 0 0 0
CH
5
Invalid measured
value or sensor
connection failure
K16
(
H10
)
0 0 0 0 0 1 0 0 0 0
CH
6
Invalid measured
value or sensor
connection failure
K32
(
H20
)
0 0 0 0 1 0 0 0 0 0
CH
7
Invalid measured
value or sensor
connection failure
K64
(
H40
)
0
0 0 1 0 0 0 0 0 0
CH
8
Invalid measured
value or sensor
connection failure
K128
(
H’80
)
0
0 1 0 0 0 0 0 0 0
Power source abnormal
K256
(
H100
)
0
1 0 0 0 0 0 0 0 0
H
ardware malfunction
K512
(
H200
)
1
0 0 0 0 0 0 0 0 0
Note:
Each error status is determined by the corresponding bit (b0~b9). Two or more errors may occur
at the same time. 0 means normal, 1 mans an error has occurred.
Communication Setting
(CR#17)
b15~b12
b11~b8
b7~b0
ASCII/RTU
Data format
Baud rate
H0
ASCII
(Default)
H0
7,E,1
(Only for ASCII)
(Default)
H02
9600
(Default)
HC
RTU
H1
8
,
E
,
1
H04
19200
H2
7
,
N
,
1
(Only for ASCII)
H08
38400
H3
8
,
N
,
1
H10
57600
H4
7
,
O
,
1
(Only for ASCII)
H20
115200
H5
8
,
O
,
1
H6
7
,
E
,
2
(Only for ASCII)
H7
8
,
E
,
2
H8
7
,
N
,
2
(Only for ASCII)
H9
8
,
N
,
2
HA
7
,
O
,
2
(Only for ASCII)
HB
8
,
O
,
2