Load Cell Module DVP02LC-SL
DVP-PLC Operation Manual
15
C R # 3 5 , 36 :
CH1 to CH2 maximum weight
Explanations:
The maximum weight set up by the user. When the value exceeds the maximum weight, bit2 and bit3
of CR#50 will be set to “1”.
C R # 3 7 , 38 , 3 9 , 4 0:
Upper/Lower limit for CH1 to CH2 zero point check
Explanations:
The references for reset to zero. When the weight is within the range, bit0 and bit1 of CR#50 will be
set to “1”.
C R # 4 1 :
Saving set value
Explanations:
The present set value is saved, and all set values are written into the internal Flash for use next
time when DVP02LC-SL is switched on. Default: 0.
When H’5678 is written in, all set values will be saved in the Flash. When the saving is completed,
CR#41 will become H’FFFF. If the value written in is not H’5678, it will automatically return to H’0,
e.g. write K1 into the CR to return it to K0.
H’0 No
action
H’FFFF
Saving is successful.
H’5678
Writing to internal Flash
C R # 4 3 , 44 :
CH1 to CH2 filter percentage
Explanations:
Range: K1 to K5. Unit: 10%. Default: K2, i.e. 20%.
C R # 4 5 , 46 :
CH1 to CH2 filter average value
Explanations:
The average weight value is displayed after the filtering. The condition to enable the filter is that the
average times have to be larger than 30.
C R # 5 0 :
Status code
Explanations:
bit
Status
bit0
H’0001
CH1 zero point weight (empty)
bit1
H’0002
CH2 zero point weight (empty)
bit2
H’0004
CH1 exceeds max. weight (overload)