When there are only 4 channels of inputs, SUB1 cannot be used for alarm output but heating/cooling control only.
**
When there are only 4 channels of inputs, OUT2 and SUB2 cannot be set up by the user but set up automatically as "alarm output” by the
controller.
Control Output:
DTE offers PID control, ON/OFF control, manual control and programmable PID control. Control output methods are set at address H10B8 ~
H10BF (default = 0: PID), PID parameters at H1028 ~ H105F, ON/OFF parameters at H1058 ~ H106F, and manual control parameters at
H1070 ~ H107F.
Alarm Output:
DTE offers 13 alarm modes. The alarm modes are set up at address H10C0 ~ H10C7, upper limits at H1080 ~ H1087 and lower limits at
H1088 ~ H108F.
SV
Alarm Mode
Alarm Output Operation
0
No alarm
Off
1
Alarm output is enabled when the temperature reaches upper and lower limits: The alarm
will be enabled when PV exceeds SV + AL-H or falls below SV – AL-L.
ON
OFF
AL-L
SV
AL-H
2
Alarm output will be enabled when the temperature reaches the upper limit: The alarm will
be enabled when the PV exceeds SV + AL-H.
ON
OFF
SV
AL-H
3
Alarm output will be enabled when the temperature reaches the lower limit: The alarm will
be enabled when the PV falls below SV – AL-L.
ON
OFF
AL-L
SV
4
Alarm output will be enabled when the PV is between SV + AL-H and SV – AL-L.
ON
OFF
AL-L
SV
AL-H
5
Alarm output will be enabled when the temperature reaches the absolute value of the
upper and lower limits: The alarm will be enabled when the PV exceeds AL-H or falls
below AL-L.
ON
OFF
AL-L
AL-H
6
Alarm output will be enabled when the temperature reaches the absolute value of the
upper limit: The alarm will be enabled when the PV exceeds AL-H.
ON
OFF
AL-H
7
Alarm output will be enabled when the temperature reaches the absolute value of the
lower limit: The alarm will be enabled when the PV falls below AL-L.
ON
OFF
AL-L
8
Upper/lower limit standby alarm: The alarm will be enabled when the PV reaches SV and
further exceeds SV + AL-H or falls below SV – AL-L.
ON
OFF
AL-L
AL-H
SV
9
Upper limit standby alarm: The alarm will be enabled when the PV reaches SV and
further exceeds SV + AL-H.
ON
OFF
SV
AL-H
10
Lower limit standby alarm: The alarm will be enabled when the PV reaches SV and
further falls below SV
–
AL-L.
ON
OFF
AL-L
SV
11
Upper limit hysteresis alarm: The alarm will be enabled when the PV exceeds SV + AL-H.
The alarm will be disabled when the PV falls below SV + AL-L.
12
Lower limit hysteresis alarm: The alarm will be enabled when the PV falls below SV
–
AL-
H. The alarm will be disabled when the PV exceeds SV
–
AL-L.
13
CT alarm: The alarm will be enabled when the CT value exceeds AL-H or falls below AL-
L.
ON
OFF
AL-L
AL-H
LED Display
PWR: On
DTE is powered.
RUN: On
Any of the channel is executing.
COM: Flashing
Communication in progress
ERR: Indicating errors (red)
ERR LED is on indicates one of the following errors occur, and the output has to be disabled.
1. Memory EEPROM error.
2. Any of the input points is not connected.
3. Any of the input points exceeds the setup range.
4. Any of the input temperatures has not been stabilized.
ON
OFF
AL-L
AL-H
ON
OFF
AL-L
AL-H