2. When you use INA input or INA + INB input, set up relevant parameters using the table below. 

INA input: 

INA 

CH1 

CH2 

CH3 

CH4 

OUT1 control mode 

10A8H 

10A9H 

10AAH 

10ABH 

OUT2 control mode 

10B0H 

10B1H 

10B2H 

10B3H 

Alarm 1 output mode 

10C0H 

10C1H 

10C2H 

10C3H 

Alarm 2 output mode 

10C4H 

10C5H 

10C6H 

10C7H 

Upper bound of Alarm 1 output 

1080H 

1081H 

1082H 

1083H 

Lower bound of Alarm 1 output   

1088H 

1089H 

108AH 

108BH 

Upper bound of Alarm 2 output 

1084H 

1085H 

1086H 

1087H 

Lower bound of Alarm 2 output 

108CH 

108DH 

108EH 

108FH 

CT value

latch

 

19A0H 

19A1H 

19A2H 

19A3H 

CT value

dynamic

 

19A4H 

19A5H 

19A6H 

19A7H 

CT adjustment value 

19A

8

19A9H 

19AAH 

19ABH 

INA + INB input: 

INA+INB 

CH1 

CH2 

CH3 

CH4 

CH5 

CH6 

CH7 

CH8 

OUT1 control mode 

10A8H 

10A9H 

10AAH 

10ABH 

10ACH 

10ADH 

10AEH 

10AFH 

Alarm 1 output mode 

10C0H 

10C1H 

10C2H 

10C3H 

10C4H 

10C5H 

10C6H 

10C7H 

Upper bound of Alarm 1 output 

1080H 

1081H 

1082H 

1083H 

1084H 

1085H 

1086H 

1087H 

Lower bound of Alarm 1 output 

1088H 

1089H 

108AH 

108BH 

108CH 

108DH 

108EH 

108FH 

CT value

latch

 

19A0H 

19A1H 

19A2H 

19A3H 

-- 

-- 

-- 

-- 

CT value

dynamic

 

19A4H 

19A5H 

19A6H 

19A7H 

-- 

-- 

-- 

-- 

CT adjustment value 

19A

8

19A9H 

19AAH 

19ABH 

-- 

-- 

-- 

-- 

3. OUT1 control mode has to be set to “0” (heating) or “1” (cooling). It cannot be set to “2” (proportional output). 

4. You can select Alarm 1 or Alarm 2 to be the output contact. The output mode has to be set to “13” (000DH). 

5. Adjust the upper/lower bound of the alarm output. 

6. The CT value will only be measured when there is OUT1 executing. If OUT1 does not exist, the previous CT value measured will be 

displayed. 

 

EVENT Input

 

Function: 

DTE10T offers 8 channels of EVENT input (EV1 ~ EV8), and each EVENT can be set up independently.   

Slot number 1 ~ 8 in AUX on DTE10T correspond to EV1 ~ EV8. 

EV1 to EV8 can be short-circuited individually with slot number 9 to switch functions. 

Hardware requirement: Accessory DTE20D inserted in the slot AUX. 

How to operate: 

1. Enable the EVENT function: Write 1234H into the address 47F1H and then 0002H into address 4824H. 

Bits in 4824H 

Bit7 

Bit6 

Bit5 

Bit4 

Bit3 

Bit2 

Bit1 

Bit0 

Flag 

-- 

Hot runner 

control 

Slop 

control 

-- 

Latch 

CT 

EVENT 

-- 

Notes: 

 

The flag to enable EVENT is at bit1 of 4824H. Write 0002H to bit1 to set it on. 

 

If the “multistate” function is enabled, for example, writing in 0022H means enabling bit5 and bit1 at the same time. 

 

You can only choose to use either the CT or EVENT function. 

Summary of Contents for DTE10P Series

Page 1: ...Separate the power cable and load wire in order to prevent interference and induced noise 7 Make sure the power cables and signal device are installed correctly before switching on the power otherwis...

Page 2: ...dbus ASCII RTU Extension port The extension port transmits 24 V power supply and communication signals to extension module DTC2000 Vibration resistance 10 to 55 Hz 10m s2 3 axes 10mins Shock resistanc...

Page 3: ...hannels of input Every channel corresponds to 2 groups of output and 2 groups of alarms OUT1 and SUB1 are for control output and OUT1 can be used for proportional output OUT2 and SUB2 are fixed for al...

Page 4: ...ed when the PV exceeds AL H or falls below AL L ON OFF AL L AL H 6 Alarm output will be enabled when the temperature reaches the absolute value of the upper limit The alarm will be enabled when the PV...

Page 5: ...e channel CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1 CT and adjustment Current Transformer Function DTE10T offers maximum 4 channels of CT CT1 CT4 responsible for monitoring the current in INA Each CT group can...

Page 6: ...A5H 19A6H 19A7H CT adjustment value 19A8H 19A9H 19AAH 19ABH 3 OUT1 control mode has to be set to 0 heating or 1 cooling It cannot be set to 2 proportional output 4 You can select Alarm 1 or Alarm 2 to...

Page 7: ...d then 0020H into address 4824H Bits in 4824H Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Flag Hot runner control Slop control Latch CT EVENT Notes The flag to enable slope function is at bit5 of 4824H Wr...

Page 8: ...Set up the time using the table below Unit second CH CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 Address for delayed alarm 1990H 1991H 1992H 1993H 1994H 1995H 1996H 1997H Output Limits Function The output is lim...

Page 9: ...The flag to enable hot runner control is at bit6 of 4824H and bit5 as to be enabled at the same time Write 0060H to set both bits on If there is already a set value in 4824H and you would like to mod...

Page 10: ...609 H104E H1709 H104F H1809 Proportional band coefficient of output 1 and output 2 0 01 99 99 Unit 0 01 H1050 H110A H1051 H120A H1052 H130A H1053 H140A H1054 H150A H1055 H160A H1056 H170A H1057 H180A...

Page 11: ...eserved H10F5 Reserved H10F6 Channel disable H10F7 Filter times Communication specifications See Table 4 H10F8 Auto ID setup H10F9 Filter range H10FA Baud rate H10FB ASCII 0 RTU 1 H10FC 8 bits 0 7 bit...

Page 12: ...0 Unit 1 min 4 Communication format H03 read bit data H06 write bit data ASCII Mode Single read and write Read Command Read Response Message Write Command Write Response Message Start word Start word...

Page 13: ...H03 Command H06 Command H06 Read start address of data H10 Length of response data byte H04 Write data address H10 Write data address H10 H00 H01 H01 Read length of data bit word H00 Data content 1 H...

Page 14: ...ngth reg_crc RTUData i i for j 0 j 8 j if reg_crc 0x01 reg_crc reg_crc 1 0xA001 else reg_crc reg_crc 1 return reg_crc Software for Setting up Communication on PC Download the free software on Delta s...

Reviews: