background image

 

7

 
In DTB series, P (Proportional Band), I(Integral Time) and D(Derivative 
Time) parameters are automatically set by using the Auto-tuning (AT) 
function. 

: This parameter is for the control mode that must be Dual Loop 

output control with PID control method configured. The value of P, I and D of 
1st output group can be set immediately. The P value of 2nd output group is 
equal to (P value of 1st output group) x 

  and the value of I and D of 

2nd output group are the same as the value of I and D of 1st output group.

: Dead Band, shown as the following figure 1, 2 and 3. This 

parameter sets an area in which the heating and cooling control output is 0 
centering around the set point in a Dual Loop output control mode. 
 

Settings lock.

 To avoid incorrect operation, two key lock functions 

are provided. 

 : Lock 1 can lock all settings. All parameters and 

temperature settings can be locked to disable changes. 

 : Lock 2 

can lock settings except the SV (Set point) value. All parameters and 
temperature settings can be locked with the exception of the SV value. 

Press 

 and 

 key simultaneously, the “Lock” status can be 

released. 

PV

0

Output

Dead band: dead
band width=negative

Set point

Heating

Cooling

Figure 3. PID

 Dead Band is negative

 control,

 

 

 

 

 

8  

Alarm 

Outputs

 

 

There are up to three groups of alarm outputs and each group allows thirteen alarm types in the initial setting 
mode. The alarm output is activated whenever the process temperature value (PV) is getting higher or lower than 
the set point of alarm limit. 

 

Set 

Value 

Alarm Type 

Alarm Output Operation

Alarm function disabled 

Output is OFF 

Deviation upper- and lower-limit:   
This alarm output operates when PV value is higher than the setting value 
SV+(AL-H) or lower than the setting value SV-(AL-L). 

ON

OFF

SV-(AL-L)

SV

SV+(AL-H)

 

2 Deviation 

upper-limit: 

 

This alarm output operates when PV value is higher than the setting value 
SV+(AL-H). 

ON

OFF

SV

SV+(AL-H)

 

3 Deviation 

lower-limit: 

 

This alarm output operates when PV value is lower than the setting value SV-(AL-L). 

ON

OFF

SV

SV-(AL-L)

 

Reverse deviation upper- and lower-limit:   
This alarm output operates when PV value is in the range of the setting value 
SV+(AL-H) and the setting value SV-(AL-L). 

ON

OFF

SV

SV-(AL-L)

SV+(AL-H)

Absolute value upper- and lower-limit:   
This alarm output operates when PV value is higher than the setting value AL-H or 
lower than the setting value AL-L. 

ON

OFF

AL-L

AL-H

Absolute value upper-limit:   
This alarm output operates when PV value is higher than the setting value AL-H. 

ON

OFF

AL-H

Absolute value lower-limit: 
This alarm output operates when PV value is lower than the setting value AL-L. 

ON

OFF

AL-L

Deviation upper- and lower-limit with standby sequence: 
This alarm output operates when PV value reaches set point (SV value) and the 
value is higher than the setting value SV+(AL-H) or lower than the setting value 
SV-(AL-L). 

ON

OFF

SV

SV-(AL-L)

SV+(AL-H)

Summary of Contents for DT4848

Page 1: ...http www delta com tw industrialautomation DELTA Temperature Controller DTB Series User Manual...

Page 2: ...e correct polarity of terminals 6 Do not install and or use the controller in places subject to Dust or corrosive gases and liquid High humidity and high radiation Vibration and shock High voltage and...

Page 3: ...de C Celsius F Fahrenheit Press this key to increase values displayed on the SV display Hold down this key to speed up the incremental action Mode key key O O O 3 Ordering Information DTB 1 2 3 4 5 6...

Page 4: ...racter 7 segment LED display Process value PV Red color Set point SV Green color Thermocouple K J T E N R S B L U TXK 3 wire Platinum RTD Pt100 JPt100 Sensor Type Analog input 0 5V 0 10V 0 20 m A 4 20...

Page 5: ...emperature set point and displays the temperature process value Use keys to set the temperature set point Setting method While in any function mode press the key to select the desired function and use...

Page 6: ...m full close to full open Display when valve control is ON Press Display and adjust output value of 1st output group Display in PID control mode and manual RUN mode Press ASCII RTU communication forma...

Page 7: ...Press to return pattern No editing mode Press to set actual step No Edit time of step No 7 of pattern No 0 unit is hh mm 7 Dual Loop Output Control Heating Cooling Control OFF PV Set point ON Heating...

Page 8: ...initial setting mode The alarm output is activated whenever the process temperature value PV is getting higher or lower than the set point of alarm limit Set Value Alarm Type Alarm Output Operation 0...

Page 9: ...t You can set current alarm range between 0 5A 30A display resolution is 0 1A and measure accuracy is 0 5A 10 EVENT Inputs Function 5 There are two optional event inputs contact inputs supported EVENT...

Page 10: ...ay on SV display 12 PID Control One group can be selected from any one of 4 groups PID parameters P I D IOF for PID control After AT PID value and temperature setting will be stored in the selected on...

Page 11: ...tents of the Temperature Sensor Type and Temperature Range for detail 1005H Control method 0 PID 1 ON OFF 2 manual tuning 3 PID grogram control 1006H Heating Cooling control selection 0 Heating 1 Cool...

Page 12: ...102BH Read pushbutton status b0 Set b1 Select b2 Up b3 Down 0 is to push 102CH Setting lock status 0 Normal 1 All setting lock 11 Lock others than SV value 102DH CT read value Unit 0 1A 102FH Softwar...

Page 13: ...0 0 02 0 0 6 0 0 02 0 mm in DTB4824 1 4 3 2 5 6 AC 100 240V 50 60 Hz 5VA Tc RTD OUT 1 DATA DATA RS 485 7 9 8 10 11 12 V OUT 2 ALM V IN L N DTB4848 65 0 min 2 56 45 0 1 77 45 0 1 77 60 0 min 2 36 0 6...

Page 14: ...9 in 9 5 mm 0 37 in 80 0 mm 3 15 in 44 75 mm 1 76 in 45 0 mm 1 77 in 0 6 0 45 0 mm 1 77 in 0 6 0 0 02 0 0 02 0 DTB4896 DTB9696 48 0 mm 1 89 in 12 8 mm 0 50 in 79 2 mm 3 12 in 91 0 mm 3 58 in 95 7 mm 3...

Page 15: ...B4848 4896 9696 Mounting Method 1 3 2 0 6 8 m m M a x 17 Error Acknowledge and Display Communication error code response description Error status 102EH 4750H PV read back 1000H 4700H Error status 0001...

Page 16: ...AN TEL 886 3 362 6301 FAX 886 3 362 7267 NORTH SOUTH AMERICA DELTA PRODUCTS CORPORATION Sales Office P O BOX 12173 5101 DAVIS DRIVE RTP NC 27709 U S A TEL 1 919 767 3813 FAX 1 919 767 3969 EUROPE DELT...

Reviews: