18
1006H
Heating/Cooling control selection Refer to Ouputput Mode Selection
1007H
1st group of Heating/Cooling
control cycle
1~990, unit is 0.1 second. When the output setting = realy, the minimum control
cycle is 5 second
1008H
2nd group of Heating/Cooling
control cycle
1~990, unit is 0.1 second. When the output setting = realy, the minimum control
cycle is 5 second 1~990
1009H
PB Proportional band
0.1 ~ 999.9
100AH
Ti Integral time
0~9,999
100BH
Td Derivative time
0~9,999
100CH
Integration default
0 ~ 100%, unit is 0.1%
100DH
Proportional control offset error
value, when Ti=0
0 ~ 100%, unit is 0.1%
100EH
The setting of COEF when Dual
Loop output control are used
0.01 ~99.99, unit is 0.01
100FH
The setting of Dead Band when
Dual Loop output control are
used
-999 ~ 9,999
1010H
Hysteresis setting value of the
1st output group
0~9,999
1011H
Hysteresis setting value of the
2nd output group
0~9,999
1012H
Output value read and write of
Output 1
Unit is 0.1%, write operation is valid under manual tuning mode only.
1013H
Output value read and write of
Output 2
Unit is 0.1%, write operation is valid under manual tuning mode only.
1016H
Temperature regulation value
-99.9 ~ +99.9. Unit is 0.1
1017H
Analog decimal setting
0 ~ 3
101CH
PID parameter selection
0~5/AUTO
101DH
SV value corresponded to PID
value
Only valid within available range, unit: 0.1 scale
1020H
Alarm 1 type
Please refer to the contents of the “Alarm Outputs” for detail
1021H
Alarm 2 type
Please refer to the contents of the “Alarm Outputs” for detail
1022H
Alarm 3 type
Please refer to the contents of the “Alarm Outputs” for detail
1024H
Upper-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail
1025H
Lower-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail
1026H
Upper-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1027H
Lower-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1028H
Upper-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
1029H
Lower-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
102AH
Read LED Status
b0: ALM3, b1: ALM2, b2: , b3: , b4: ALM1, b5: OUT2, b6:OUT1, b7: AT
℉
℃
102BH
Read Pushbutton Status
b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key
102CH
Setting lock status
102FH
Software version
V1.00 indicates 0x100
1030H
Start pattern number
0 ~ 15
1200H~13FFH
Pattern 0~15 temperature set
point setting (Even number)
Pattern 0~15 execution time
setting (Odd number)
-999 ~ 9999
Time: 0 ~ 900
(
1 minute per scale
)
1400H~140FH
Actual number of step setting
inside the corresponding pattern
0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N
1410H~141FH
Cycle number for repeating the
execution of the correspond
pattern
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
1420H~142FH
Link pattern number setting of
the correspond pattern
0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the
program end and execution end. 0~15 indicates the next execution pattern
number after executing the current pattern
Address
Content
Definition
1100H Adjust
Temperature
Gain
1101H
Temperature Filter Range
Range of temperature filter: 10~1000, unit: 0.01
℃
, default: 100(1.0
℃
)
1102H
Temperature Filter Factor
Setting range: 0~50, default: 8