selection 

0812H 

Decimal point position selection 

0: No decimal place 1: decimal place. (Except for the thermocouple B,S,R type, 
all other thermocouple type are valid.) 

0813H 

AT setting 

OFF: 0 (default), ON : 1 

0814H 

Control RUN/STOP setting   

0: STOP, 1: RUN (default) 

0815H 

STOP setting for PID program 
control  

0: RUN (default), 1: STOP 

0816H 

Temporarily STOP for PID program 
control  

0: RUN (default), 1: Temporarily STOP 

2.  Communication Transmission Format: Command Code: 02: read bits, 05: write bit, 03: read words, 06: write 1 word 

ASCII Mode

 

Read Command

 

Read Command Response

 

Write Command 

Write Command Response 

STX 

’: ’ 

’: ’ 

STX 

’: ’ 

’: ’ 

STX 

’: ’ 

’: ’ 

STX 

’: ’ 

’: ’ 

ADR 

1 ‘0’ 

‘0’ ADR 

1 ‘0’ 

‘0’ ADR 

1 ‘0’ 

‘0’ ADR 

1 ‘0’ 

‘0’ 

ADR 

0 ‘1’ 

‘1’ ADR 

0 ‘1’ 

‘1’ ADR 

0 ‘1’ 

‘1’ ADR 

0 ‘1’ 

‘1’ 

CMD 

1 ‘0’ 

‘0’ CMD 

1 ‘0’ 

‘0’ CMD 

1 ‘0’ 

‘0’ CMD 

1 ‘0’ 

‘0’ 

CMD 

0 ‘3’ 

‘2’ CMD 

0 ‘3’ 

‘2’ CMD 

0 ‘6’ 

‘5’ CMD 

0 ‘6’ 

‘5’ 

‘1’ ‘0’ 

‘0’ ‘0’ 

‘1’ ‘0’ 

‘1’ ‘0’ 

‘0’ ‘8’ 

Number of data 

(count by byte) 

‘4’ ‘2’ 

‘0’ ‘8’ 

‘0’ ‘8’ 

‘0’ ‘1’ 

‘0’ ‘1’ 

‘0’ ‘1’ 

‘0’ ‘1’ 

Starting data 

address 

‘0’ ‘0’ 

‘1’ ‘7’ 

Starting data 

address 

‘1’ ‘0’ 

Starting data 

address 

‘1’ ‘0’ 

‘0’ ‘0’ 

‘F’ ‘0’ 

‘0’ ‘F’ 

‘0’ ‘F’ 

‘0’ ‘0’ 

Start address 

data 

1000H/081xH  

‘4’ ‘1’ 

‘3’ ‘F’ 

‘3’ ‘F’ 

‘0’ ‘0’ 

‘0’   

‘E’ ‘0’ 

‘E’ ‘0’ 

Number of data 

(word/Bit) 

‘2’ ‘9’ 

‘0’   

Data content

‘8’ ‘0’ 

Data content 

‘8’ ‘0’ 

LRC 1 

‘E’ 

‘D’ 

‘0’ 

 

LRC1  

‘F’ 

‘E’ 

LRC1  

‘F’ 

‘E’ 

LRC 0 

‘A’ 

‘C’ 

Address data 

1001H 

‘0’ 

 

LRC 0   

‘D’

‘3’ 

LRC 0   

‘D’ 

‘3’ 

END 1 

CR 

CR 

LRC 1 

‘0’ 

‘E’ 

END 1 

CR

CR

END 1 

CR 

CR

END 0 

LF 

LF 

LRC 0 

‘3’ 

‘3’ 

END 0 

LF

LF

END 0 

LF 

LF

  

 

END 

CR

CR

  

   

 

  

 

END 

LF

LF

  

   

 

LRC checksum:   

LRC check is the added sum from “Address” to “Data content”. For example, 01H + 03H + 10+ 00H + 00H + 02H = 16H, then take the 

complementary of 2, EAH.   

RTU

 

Mode 

Read Command

 

Read Command Response

 

Write Command 

Write Command Response 

ADR 01H 

01H ADR 01H

01H

ADR 01H

01H

ADR 01H 

01H

CMD 03H 

02H CMD 03H

02H

CMD 06H

05H

CMD 06H 

05H

10H 08H 

10H

08H

10H 08H

Starting data 

address 

00H 10H 

Number of data 

(count by byte) 

04H

02H

Starting data 

address 

01H

10H

Starting data 

address 

01H 10H

00H 00H 

01H

17H

03H

FFH

03H FFH

Number of data   

(word/Bit) 

02H 09H 

Start address 

data 

1000H/081xH 

F4H

01H

Data content

20H

00H

Data content 

20H 00H

CRC 1 

C0H  BBH 

03H

 

CRC 1 

DDH

8FH

CRC 1 

DDH

8FH

CRC 0 

CBH  A9H 

Address 

data1001H 

20H

 

CRC 0 

E2H

9FH

CRC 0 

E2H

9FH

 

  

CRC 

1 BBH

77H  

   

  

 

  

CRC 

0 15H

88H  

   

  

CRC (Cyclical Redundancy Check) is obtained by the following steps. 

1. Load in a 16-bit register FFFFH as the CRC register. 

2. Do an exclusive OR operation of the first byte of the data and low byte of CRC register, and place the operation result back to 

the CRC register. 

3. Right shift the bits in the CRC register and fill the high bits with “0”. Check the removed lowest bit. 

4. If the removed lowest bit is “0”, repeat step 3. Otherwise, do an exclusive OR operation of the CRC register and the value 

A001H and place the operation result back to the CRC register. 

5. Repeat step 3 and 4 until the 8 bits (1 byte) are all right shifted.   

6. Repeat step 2 and 5 and calcualte all the bits to obtain CRC check. 

Please be aware of the high/low byte transmission order in the CRC register. 

Summary of Contents for DT3 Series

Page 1: ...ecting a platinum resistance thermometer RTD 10 Please keep the wire as short as possible when wiring a platinum resistance thermometer RTD to the controller and please route power wires as far as possible from load wires to prevent interference and induced noise 11 This controller is an open type unit and must be placed in an enclosure away from high temperature humidity dripping water corrosive ...

Page 2: ...ections Ambient Temperature 0 C 50 C Storage Temperature 20 C 65 C Altitude Max 2000m Relative Humidity 35 80 RH non condensing Operation There are three modes of operation operation regulation and initial setting When power is applied controller gets into the operation mode Press the key to switch to regulation mode If the key is pressed for more than 3 seconds controller will switch to the initi...

Page 3: ... to Temperature Sensor Type Temperature Range Chart for the selection of Thermocouple or Platinum Resistance types PT TEMP UNIT Set temperature unit it wil not be displayed when in analog input mode TEMP HIGH Set up upper temperature limit the upper limit setting is different for different types of sensor 850 0 TEMP LOW Set up lower temperature limit the lower limit setting is different for differ...

Page 4: ...elect P value accordingly 47 6 I Integral Time Setting display when Crtl PID FUZZY this parameter is set automatically when TUNE AT Set I value according to the selection of PID No n 0 5 When I is set to AUTO the system will select I value accordingly 260 D Deviation Time SEtting display when Crtl PID FUZZY this parameter is set automatically when TUNE AT Set D value according to the selection of ...

Page 5: ...ect the n th PID n 0 5 press to set 0 5 th PID parameters Set up the 0 th PID temperature value press V Set up the 5 th PID temperature value press V Set up the 0 th proportional band value Set up the 5 th proportional band value Set up the 0 th Ti value Set up the 5 th Ti value Set up the 0 th Td value Set up the 5 th Td value Set up the 0 th PID integral deviation Press to set the parameters in ...

Page 6: ...r to change the PV and SV display unit select decimal point and switch between F In Operation Mode SP 1 displays decimal place ex 25 5 degree SP 0 displays integral number ex 25 degree In Initial Setting Mode Select temperature display unit 9 5 32 Set Value and the Upper Lower Limit of Input Value Setting Set the Upper Limit of Input Value This parameter can be set in the Initial Setting Mode the ...

Page 7: ... linear voltage output 0 10V user s desire output value can be attained by using compensation function For example the analog output 1 can be adjusted in and parameters in Regulation Mode The output value can be positive or negative and it can be changed by pressing the Up Down key on the temperature controller The scale of each pressing is an increase or decrease of 1uA and 1mV For example To cha...

Page 8: ...rent output L Linear voltage output S SSR output SV 3 rd digit indicates the function of accessory 2 N No function C CT measure E EVENT1 input R REMOTE input SV 4 th digit indicates the function of accessory 3 N No function C CT measure E EVENT2 input R RETRANSMISSION output Selection for Heating Cooling Alarm Dual Loop Output Control DT3 series offers 1 set of Output Control OUT1 that is built in...

Page 9: ...p to the target temperature After setting these parameters each temperature controller will have its own set of initial pattern and initial step for creating its own temperature setting curve Some of the terms are explained as follows a Initial pattern set the program to start running at a sequential number of patterns b Initial Step set the program to start running at a sequential number of steps...

Page 10: ...lue can be dynamic an analog value voltage or current can be converted into a dynamic input value Two methods can be used for the conversion positive slope or negative slope they are depicted as follows a Positive slope Remote setting Display of Remote analog input is in positive proportion with setting input e g Remote input type is selected as 1 5 V analog voltage Remote higher limit of input is...

Page 11: ... via auto tuning AT a A total of six sets of PID parameters are available one of which can be selected for carrying out PID and the program may automatically select a set of PID that is most close to the input value In order to achieve this each set of PID parameters has a reference input setting value which allows the user to set for manual setting or for auto tuning AT E G for the six sets of PI...

Page 12: ... manual control is 20 You may force a fixed output value after a switchover for example controlling the output to be 40 b Switch from manual control to PID control if manual control before switching over to PID control is 40 the program will take 40 as the initial value for calculating the PID value and output the new control Note If power of machine is switched off in manual control mood the outp...

Page 13: ...ion Mode z Self_Tuning By full output of heating or cooling max slope of temperature alteration and system delay can be attained from the Temperature Time Curve and P I D IOF parameters can be calculated Self tuning can be carried out in RUN mode and in STOP mode In the RUN mode PID parameters are allowed to be updated when the machine is running in the STOP mode PID parameters for the SV value ca...

Page 14: ...er Setting of F1 F2 function keys In the Operation Mode PV SV display mode pressing a function key more than 3 seconds will prompt you to the setting of the following functions press keys to make a selection Function Description MENU When in a screen other than the PV SV display mode pressing F1 F2 key continuously may save the setting to quickly switch the menu screen When the screen shows KEY SA...

Page 15: ...to in Operation Mode At the same time press and keys for 3 seconds to display and enter Password 1357 The screen displays Parameter reset selecting will overwrite all user settings with factory settings Key Lock Function Adjusting parameter to in Operation Mode will lock all keys adjusting the parameter to allows adjustment of SV setting values and F1 F2 function keys Unlock the key Press and keys...

Page 16: ...n PV value is higher than the setting value SV AL H or lower than the setting value SV AL L ON OFF SV AL L SV SV AL H 2 Deviation upper limit This alarm output operates when PV value is higher than the setting value SV AL H ON OFF SV SV AL H 3 Deviation lower limit This alarm output operates when PV value is lower than the setting value SV AL L ON OFF SV AL L SV 4 Absolute value upper and lower li...

Page 17: ... Use the parameters in Initial Setting Mode to set the digit Y of value Yxxx when Y 0 normal operation Y 1 peak signal Note Refer to the table PV Color Change Function This controller provides PV color change function The PV display color will be changed if the selected alarm energized Use the parameter PV color in Initial Setting Mode to select the alarm selectable items are and RS 485 Communicat...

Page 18: ...nts of the Alarm Outputs for detail 1024H Upper limit alarm 1 Please refer to the contents of the Alarm Outputs for detail 1025H Lower limit alarm 1 Please refer to the contents of the Alarm Outputs for detail 1026H Upper limit alarm 2 Please refer to the contents of the Alarm Outputs for detail 1027H Lower limit alarm 2 Please refer to the contents of the Alarm Outputs for detail 1028H Upper limi...

Page 19: ...of Analog Linear Output 1 Adjust current 1scale 1μA Adjust voltage 1scale 1mV 1118H Adjust Upper Limit of Analog Linear Output 2 Adjust current 1scale 1μA Adjust voltage 1scale 1mV 1119H Adjust Lower Limit of Analog Linear Output 2 Adjust current 1scale 1μA Adjust voltage 1scale 1mV 111AH Adjust Retransmission Upper Limit Adjust current 1scale 1μA 111BH Adjust Retransmission Lower Limit Adjust cur...

Page 20: ... added sum from Address to Data content For example 01H 03H 10 00H 00H 02H 16H then take the complementary of 2 EAH RTU Mode Read Command Read Command Response Write Command Write Command Response ADR 01H 01H ADR 01H 01H ADR 01H 01H ADR 01H 01H CMD 03H 02H CMD 03H 02H CMD 06H 05H CMD 06H 05H 10H 08H 10H 08H 10H 08H Starting data address 00H 10H Number of data count by byte 04H 02H Starting data ad...