21
6.3.7 Restore Settings
■
Default: Restores settings on the meter to factory default.
■
Energy: Resets to zero for the value of electrical energy accumulated on the meter and that calculated
without a meter-checking personnel.
■
Demand: Resets to zero for the currents calculated by the meter, value of power demand, and logged
time and date.
■
Alarm: Clears away all alarm logs detected on the meter.
■
MaxMin: Clears away all records of maximum and minimum values logged on the meter.
■
Data Log: Clears away all historical data logs that are stored in the memory on the meter.
■
Clear All: Restores all settings on the meter to factory default and clears away all historical data logs.
■
Steps to set up are as follows:
(1) Press Menu key until the menu appears.
(2) Select 0. Setup and press Enter key to enter into the setup menu.
(3) Select 8. Reset and press the Enter key to enter into options.
(4) Select the setup item needed and press the Enter key to enter into the option.
(5) Press the Enter key to start setting up.
(6) When the option is highlighted, start setting up by using the Up and Down keys to select the mode
needed.
(7) Press the Enter key to complete. When the highlight disappears, setup is complete. If there is a
need to cancel the setup in the middle, press the Menu key to return without saving the mode that
was just selected.
(8)
Repeat steps (6)~(7) until finishing setup for the last number and press the Enter key. When the
highlight disappears, setup is complete. If there is a need to cancel the setup in the middle, press
the Menu key to return without saving the numbers that were just set.
(9) After completing or cancelling the setup, press the Menu key again to return to the setup menu.