background image

Description

This 24 Vac, non-spring return electronic actuator is designed for modulating 

and three-position control of building HVAC valves and dampers.

Features 

 

• Brushless motor technology with stall protection

 

• Unique self-centering shaft coupling

 

• Manual override

 

• 132 lb-in (15 Nm) torque

 

• 5° preload as shipped from factory

 

• Mechanical range adjustment capabilities

 

• Offset and span adjustment models available

 

• Models with independently adjustable, dual auxiliary switches available

 

• Built-in 1/2-inch conduit connection

 

• UL and C-UL listed, CE certified

DC-132 Non Spring Return Electronic Actuator Series

Delta Control Products, Inc.
2031 West Rose Garden Lane
Phoenix, AZ 85027
623-780-2408

Product Numbers 

Table 1. 

Operating

Voltage

Control

Built-in Control

Options 

Product

Number 

DC24-132-T

DC24-132-TA 

DCM24-132 

DCM24-132-ZA 

24 V

AC ±20%

Modulating 0-10 VDC

3-Position (T

ri-State)

Position Feedback

Dual Auxiliary Switches

Of

f-Set and Span

Input Signal Selectable

Summary of Contents for DC-132 Series

Page 1: ...n adjustment models available Models with independently adjustable dual auxiliary switches available Built in 1 2 inch conduit connection UL and C UL listed CE certified DC 132 Non Spring Return Elect...

Page 2: ...ion 25 F to 130 F 32 C to 55 C Storage and transport 40 F to 158 F 40 C to 70 C Ambient humidity non condensing 95 rh UL60730 to replace UL873 C UL certified to Canadian Standard C22 2 No 24 93 Contro...

Page 3: ...the control signal A 0 to 10 Vdc position feedback output signal is available between wire 9 U and wire 2 G0 to monitor the position of the damper motor In the event of a power failure the actuator ho...

Page 4: ...ge of shaft movement is limited by mounting the shaft adapter 1 Loosen the shaft adapter from the damper shaft and remove the actuator from the damper shaft 2 Remove the clip and shaft adapter from th...

Page 5: ...0 V Calculating the value of U U 16 V 100 Umax Umin 100 x 10 2 Working angle of rotation in 50 Uo 2 U 16 V Umin minimum control signal Umax maximum control signal 100 0 U 16 V YU v YS 2 18 10 Umin Uma...

Page 6: ...ations Use earth ground isolating step down Class 2 transformers Do not use autotrans formers The maximum rating for a Class 2 step down transformer is 100 VA Determine the supply transformer rating b...

Page 7: ...16 141 8 3 8 212 1 11 16 42 1 3 16 30 1 3 16 30 1 8 3 min 4 100 min 6 150 min 2 3 8 60 min 4 100 3 ft 900 2 3 8 60 1 2 NSPT 1 2 12 3 4 19 47 5 47 5 min 4 100 3 25 83 Figure 12 Dimensions of the DC 13...