background image

Operating voltage  

24 VAC ±20%

Frequency  

 

50/60 Hz

Power consumption
 Running:
 

 

DCM24-132, DCM24-132-ZA 

5 VA/4W

 

 

DC24-132-T, DC24-132-T  

3 VA/3W

 Holding:
 

 

DCM24-132, DCM24-132-ZA 

1 VA/1W

Equipment rating  

Class 2, in accordance with UL/CSA

 

 

 

Class III per EN 60730

Input signal (wires 8-2) DCM24-132, DCM24-132-ZA
 

Voltage-input  

0 to 10 Vdc (max. 35 Vdc)

 

Input resistance  

>100K ohms

Position output signal (wires 9-2) DCM24-132, DCM24-132-ZA
 

Voltage-output  

0 to 10 VDC

 

Maximum output current  

±1 mA

Running torque  

132 lb-in (15 Nm)

 

Maximum torque 

265 lb-in (30 Nm)

Runtime for 90° opening or closing
 

60 Hz  

125 seconds

 

50 Hz  

150 seconds

Nominal angle of rotation  

90°

Maximum angular rotation  

95°

Shaft size  

 

1/4 to 3/4-inch (6.4 to 20.5 mm) dia.

 

 

 

1/4 to 1/2-inch (6.4 to 13 mm) square

Minimum shaft length  

3/4-inch (20 mm)

Enclosure  

 

NEMA 1

 

 

 

IP54 according to EN 60 529

Material  

 

Die cast aluminum alloy

Gear lubrication  

Silicone free

Ambient temperature
 

Operation  

-25°F to 130°F (-32°C to 55°C)

 

Storage and transport 

 -40°F to 158°F (-40°C to 70°C)

Ambient humidity (non-condensing)  

95% rh

 
 

 

 

UL60730 (to replace UL873)

 

 

 

C-UL certified to Canadian Standard

 

 

 

C22.2 No. 24-93

Control signal adjustment (-Z Models)
 

Offset (start point)  

Between 0 to 5V

 

Span Between  

2 to 30V

Dual auxiliary switches (A Models)
 

AC rating  

24 to 250 Vac

 

 

 

AC 6A resistive,

 

 

 

AC 2A general purpose

 

DC rating  

12 to 30 Vdc

  

 

DC 

2A

Switch Range
 

Switch A  

0 to 90° with 5° intervals

 

Recommended range usage  

0 to 45°

 

Factory setting 

 5°

 

Switch B  

0 to 90° with 5° intervals

 

Recommended range usage  

45 to 90°

 

Factory setting  

85°

Switching hysteresis  

Feedback potentiometer DCM (Modulating Units)  

0 to 1000 ohm <10 mA

 

Voltage  

UL-Class 2 (SELV/PELV for CE)

Pre-cabled connection  

18 AWG

Cable length    

3 feet (0.9m) length

Life cycle  

 

Designed for over 50,000 full strokes

 

 

 

at rated torque and temperature

Dimensions:    

Inches (mm) 8-3/8 H × 3-1/4 W × 2-2/3 D

 

 

 

(212 H × 83 W × 68 D)

Weight    

 

2.2 lbs. (1 kg)

Power Supply
24 VAC

Control Signal

Feedback Signal 

Function 

Mounting 

Housing 

Ambient Conditions

Agency Certification

Auxiliary Features

Miscellaneous

Specifications

PAGE 2

Summary of Contents for DC-132 Series

Page 1: ...n adjustment models available Models with independently adjustable dual auxiliary switches available Built in 1 2 inch conduit connection UL and C UL listed CE certified DC 132 Non Spring Return Elect...

Page 2: ...ion 25 F to 130 F 32 C to 55 C Storage and transport 40 F to 158 F 40 C to 70 C Ambient humidity non condensing 95 rh UL60730 to replace UL873 C UL certified to Canadian Standard C22 2 No 24 93 Contro...

Page 3: ...the control signal A 0 to 10 Vdc position feedback output signal is available between wire 9 U and wire 2 G0 to monitor the position of the damper motor In the event of a power failure the actuator ho...

Page 4: ...ge of shaft movement is limited by mounting the shaft adapter 1 Loosen the shaft adapter from the damper shaft and remove the actuator from the damper shaft 2 Remove the clip and shaft adapter from th...

Page 5: ...0 V Calculating the value of U U 16 V 100 Umax Umin 100 x 10 2 Working angle of rotation in 50 Uo 2 U 16 V Umin minimum control signal Umax maximum control signal 100 0 U 16 V YU v YS 2 18 10 Umin Uma...

Page 6: ...ations Use earth ground isolating step down Class 2 transformers Do not use autotrans formers The maximum rating for a Class 2 step down transformer is 100 VA Determine the supply transformer rating b...

Page 7: ...16 141 8 3 8 212 1 11 16 42 1 3 16 30 1 3 16 30 1 8 3 min 4 100 min 6 150 min 2 3 8 60 min 4 100 3 ft 900 2 3 8 60 1 2 NSPT 1 2 12 3 4 19 47 5 47 5 min 4 100 3 25 83 Figure 12 Dimensions of the DC 13...

Reviews: