Chapt er 7 S t udi o 500 0 S of t war e O per at i on
7 - 1 3
7_
You will see the TAGs listed under the Name section. TAGs will be shown with a product name in the front and a
C/I1/O1 in the back, separated by a colon (:), for example CMCEIP01:C, CMCEIP01:I1, and CMCEIP01:O1.
TAG
:
C contains information from Adapter EDS file, including Input and Output parameters. Users can edit the
parameters of Input and Output here.
TAG
:
I1, the mapping starts from TAG
:
I1[0], and will be mapped to the first parameters of the Adapter Output. The
length is the output length provided by the Adapter.
TAG
:
O1, the mapping starts from TAG
:
O1[0], and will be mapped to the first parameters of the Adapter Input. The
length is the input length provided by the Adapter.
Tag:I1[0]
Tag:I1
Tag:I1[1]
Tag:I1[31]
Parameter_0
Parameter_1
Parameter_31
Adapter
Output
Tag:O1[0]
Tag:O1
Tag:O1[1]
Tag:O1[31]
Parameter_0
Parameter_1
Parameter_31
Adapter
Input
Delta Adapter
VFD-C2000
RA EIP Scanner
1756-L71+1756-EN2TR
EtherNet/IP
..
.
..
.
..
.
..
.