C h a p t e r 4 E I P B u il d e r
4 - 2 7
4_
c) Select TAG to have this function enabled. And after this function is enabled, the attributes is
read only (
).
※
Users can also select TAG and then input the IP address directly to connect to TAGs from other
devices. In this case, there is no need to create a connection to Gerneal Device.
d) Users can use the drop-down list of the CPU Address /TAG to select the already created
Consumed TAG.
e)
After the TAG function is selected, the system will input data in the columns of Adapter register
address, parameter, and address of the TAG with the same name. Users can also edit the data
in the columns. Make sure the TAG name is the same as the Produced TAG of the EIP to be
connected
.
Set up property
a) Click the Property to set up.
b) Type the data mapping parameters
Set the Requested Packet Interval (RPI) to renew the data between the Scanner and Adapter
cyclically, for example every 20ms.