background image

PROBLEM SOLVING & MAINTENANCE SUGGESTIONS



We recommend that you use only genuine Delta

®

 replacement parts to maintain the warranty.



DO NOT USE EXCESSIVE FORCE

 to close the inlet stop stem. We 

RECOMMEND

 that the flushometer be flushed while closing the inlet stop. The noise 

created by the water flow or the flow into the fixture will stop when the inlet water is shut off.

NO LIGHTS - NO POWER

1.  Check that the four “AA” batteries are positioned properly in the battery holder. Use the +/- signs on the batteries and the +/- signs on the battery holder for 

correct positioning.

2.  If the batteries are positioned correctly, but there are still no lights, replace with four new “AA” Alkaline batteries (“TO REPLACE BATTERIES (see Figure 

15)” on page 12).

3.  Check for damage or corrosion of the battery terminals in the battery holder. Replace battery holder (060334A, item #3) if necessary.

EXCESSIVE NOISE

1. 

PARTIALLY

 close the inlet stop.

2.  Pressures OVER 75 PSI may lead to an increase in 

NOISE

, water could 

SPLASH

 out of the fixture more easily and the 

LIFE

 of any plumbing valve may 

be 

SHORTENED

.

3.  Install a Pressure Reducing Valve set at a lower pressure if actual pressure is over 75 PSI. While the TECK Flushometer will operate up to 125 PSI, the 

preferred operating range is between 35 and 65 PSI.

4.  On flushometers that have been installed for a number of years, check the Renewable Seat (062007A, item #11) for wear and replace if necessary.

EXCESSIVE WATER FLOW RATE

1. 

OPEN

 inlet stop 

ONE TURN

 and adjust Regulating Screw (061024A, item #7) to the fixture requirement (except on models that have a fixed volume).

2.  Operation of flushometer with inlet stop 

BELOW ONE TURN OPEN

 may cause 

EXCESSIVE NOISE

. The lowest open setting for the inlet stop may vary 

depending on the installation.

SHORTAGE OF WATER TO PROPERLY FLUSH BOWL

1. 

OPEN

 inlet stop fully.

2. 

CHECK

 pipeline for size or obstruction, partially closed gate or other supply line valve, corroded or under size water piping.

3. 

CHECK

 water pressure.

4.  Water flow rate is determined by 

BOTH 

the water pipe size 

AND

 the water pressure available.

5.  A water closet flush valve requires a minimum water supply of 1” (or larger), depending on a number of different factors including water pressure (PSI) 

available, pipe size and length of pipe run, number of fixtures per washroom and per building, fixture type, fixture usage factor, elevation of valve above the 

water main, etc. We strongly recommend that pipe size calculations be done to insure proper water supply sizes.



Flushometers 

DO NOT

 provide a water supply; they are merely automatically timed self-closing valves. The inlet supply piping is the water reservoir that 

must supply sufficient water volume in a short period of time (4 to 10 seconds) to properly flush and clear the fixture.

CONTINUOUS FLUSHING

1.  The Regulating Screw (061024A, item #7) may be turned 

RIGHT

 (clockwise) 

TOO FAR

. Adjust by slowly turning the Regulating Screw 

LEFT

 (counter-

clockwise) (except -48, -42, -19 and -05 models, which are fixed volume).

2.  If flush is still continuous, close inlet stop, remove Regulating Screw (061024A, item #7), 

CLEAN

 bypass slot in the Screw, 

REPLACE

 it in the valve and 

ADJUST

 slowly for proper flush (except on models that have a fixed volume).

3.  Remove cap assembly (item #8) and Diaphragm/Guide Assembly (061323A - W/C, item #10a or 061324A - UR, item #10b), check for contaminants at 

renewable seat (062007A, item #11) and diaphragm and check for debris in the cap for blockage. Also 

CHECK

 that the Diaphragm/Guide slides easily in 

the Renewable Seat.

4.  If sensor is picking up a reflective surface, or flushes when someone walks by, range too long; shorten range or adjust sensor angle (“Sensor Angle 

Adjustment / Réglage de l’angle du capteur” on page 10).

VALVE WILL NOT FLUSH

1.  When the valve has been taken apart for servicing and re-assembled and 

DOES NOT

 operate, check that the Cap has been put on the body properly. The 

Regulating Screw (061024A, item #7) should always be on the same side as the inlet stop.

2.  When all lights operate as expected but valve will not flush, check that the solenoid wires are connected and the solenoid is making a clicking sound. If no 

clicking sound is present, then replace with cap/solenoid & regulating screw assembly (item #8).

3.  If the valve will flush but shuts off immediately when activated, the Diaphragm (060079A-MMO, item #10c) may be worn or split and need to be replaced.
4.  The flushometer may not detect a user if the toilet seat is left in an upright position. This can be due to the Flushometer being installed too low or there is 

no gap in the front toilet seat. Adjust the height of the valve or change the toilet seat. 

5.  The sensor may have trouble detecting certain types of clothing material.

SLIGHT WATER LEAK INTO FIXTURE

1. 

EXAMINE

 the seating surface of the Diaphragm (060079A-MMO, item #10c) for embedded sediment.

Page - 16 of 19

213104 Rev. A

Summary of Contents for 81T201SP-MMO

Page 1: ...d flush Urinal only DF Dual Flush Option AUTRES VOLUMES DE CHASSE Vide Chasse d eau r glable toilette et urinoir 42 chasse fixe de 4 2 Lpf 1 1 gpf seulement pour les toilettes 48 chasse fixe de 4 8 Lp...

Page 2: ...s and longer life for the working parts Le robinet de chasse doit tre combin un appareil sanitaire au volume de chasse quivalent APPROVISIONNEMENT EN EAU RECOMMAND Toilette Pression de courant minimum...

Page 3: ...T place the sensor of one Flushometer across from another Flushometer see Figure 2 C W voir Figure 2 Pour viter tout dysfonctionnement de la vanne ne pas installer une main courante ou tout autre obje...

Page 4: ...important de RINCER et de bien NETTOYER les conduites d eau pour LIMINER les contaminants par exemple calcaire s diments gravier boutures soudure etc Lorsque l eau a un contenu lev de s diments un fil...

Page 5: ...et coupez une longueur quivalente la distance mesur e dd du tube de sortie inf rieur E Si la queue de la soupape de vidange A1 est au dessous de la soupape d arr t H vous devez commander le tube de so...

Page 6: ...doit liminer tout l air dans la soupape de vidange NE PAS R GLER le volume d eau de la soupape de vidange bas sur les r sultats de la premi re chasse d eau IF LEFT HAND STOP IS REQUIRED see Figure 6...

Page 7: ...sous voir Figure 8 La vis de r gulation G peut tre r gl e selon les conditions de travail et l appareil install au volume d eau appropri pour l appareil particulier Mod les r glables Volumes de chasse...

Page 8: ...or Light The Dual Flush Water Closet Flushometer models have 4 settings that are adjustable via the Set up Mode a Bowl Length Selection b Dual Flush Mode c 24 hour Flush Adjustment and d Indicator Lig...

Page 9: ...e de r glage passez par les modes de r glage dans l ordre d crit ci dessous voir Figure 10 a Utilisez le bouton bleu B sur le capteur pour faire d filer les diff rentes options pour chaque param tre b...

Page 10: ...une cible la fin du bol iii Le voyant bleu clignotera et la soupape de vidange s activera confirmant que le capteur est configur pour cette longueur de cuve aa Ajustez le r glage et r p tez le test si...

Page 11: ...be DAMAGED by ACIDIC CLEANERS example cleaners designed specifically for vitreous china lavatories and water closets HARSH ABRASIVES or POLISH To clean simply wipe the surface with a damp cloth and bl...

Page 12: ...ioning DO NOT use a 9 volt battery as a replacement for the four AA Alkaline batteries 5 Install the refreshed Battery Holder E back into the cover and reconnect battery connection When the new batter...

Page 13: ...11 10a 9a 7 8 5 24 13 21 22 14 15 17 27 16 25 6 9c 9b 12 23 18 30 31 32 28 29 26 10b 10c 19 20 1 2 3 4 Repair Parts Pi ces de Rechange Page 13 of 19 213104 Rev A...

Page 14: ...See Table 1 Assemblage du guide de diaphragme pour les urinoirs voir Tableau 1 10c 060079A MMO Diaphragm only 12 pkg Diaphragme seulement 12 pqt 11 062007A Brass Seat with O Ring Si ge en laiton avec...

Page 15: ...e r glage 061353A 061374A 061356A 061354A 061355A 061325A Poppet Pin Tige Clapet 060508A 060507A 060507A 062025A Diaphragm Assembly Ensemble Guid Diaphragme 061324A 061323A Must use all noted componen...

Page 16: ...fixture type fixture usage factor elevation of valve above the water main etc We strongly recommend that pipe size calculations be done to insure proper water supply sizes Flushometers DO NOT provide...

Page 17: ...e type de dispositif le facteur d usage du dispositif l altitude de la vanne au dessus de la conduite principal etc Nous vous recommandons fortement de faire les calculs des dimensions du tuyau afin d...

Page 18: ...HICHEVER IS SHORTER Some states provinces do not allow limitations on how long an implied warranty or condition lasts so the above limitation may not apply to you Limitation of Special Incidental or C...

Page 19: ...AL OU LA DUR E DE CETTE GARANTIE SOIT LA DUR E LA PLUS COURTE DES DEUX Certains tats ou provinces ne permettent pas de limitation la dur e d une garantie ou condition implicite ainsi les limitations c...

Reviews: