background image

15

5 Introduction of DIP Switch

5.1 Function DIP Switch S7

 

  CAUTION !

Functional DIP switch S7 is located on the mainboard of the indoor unit. It is operated when the user 
needs to change the default setting. 

Functional DIP switch S7

DIP switch

Functional description:

DIP switch setting

0 (ON Position)

1

1(S / R)

Setting of memory mode

Standby (S)

Restore (R)

2(L / I)

Setting of control mode

Wired control (L)

Remote control (I)

3(M / S)

Setting of master/Slave indoor unit

Master indoor unit (M)

Slave indoor unit (S)

Functional description of function DIP switch:

DIP switch 1 (S/R): 

Setting of memory mode, including the standby mode and restoration mode. The standby 

mode refers to that the previous parameters will be kept but the unit will not run automatically after 
the power supply is resumed. This DIP switch is factory defaulted to be at the “ON” position. For 
example, if the parameters of an indoor unit set before power shutdown are High Fan and 24°C, 
the unit will be under standby state after the power supply is resumed and after the unit is manually 
started, the parameters will remain as High Fan and 24°C. The restoration mode refers to that not 
only the previous parameters will be kept, but also that the unit can start automatically after the 
power supply is resumed. But if the unit is under STOP state before power failure, it will be also 
under STOP state after the power supply is resumed.

DIP switch 2 (L/I): 

Setting of the control mode through either the wired controller or the remote controller. When 

it is under the wired controller mode, the “Setting of Momory Mode” of switch 1 and the “Setting 
of Master/Slave Unit” of switch 3 can only be set through the wired controller. when it is under the 
remote controller, both two settings can still be set through this function DIP switch S7. 

DIP switch 3 (M/S): 

The setting of master/save indoor unit is intended to set which units as the master units and 

which as the slave units, mainly used to meet the needs of speical people given priority (eg. 

leaders, patients, etc.). All indoor units are factory defaulted to be master units, with this switch set 

to the “ON” position.

When all indoor units are set as the slave units, the mode of that who start first will always 

takes precedence. If its mode conflicts with that of the unit started later, then the unit started later 
will raise a conflict mode error and stop working. In this case, it is easily understood that the mode 
of the unit which starts first always takes precedence.

When only one indoor unit is set as the master unit, no mater if it is firstly started or not, if its 

mode conflicts with that of any slave unit, then this slave unit will raise a mode conflict error and 

stop working. In this case, it is easily understood that the mode of the master unit always takes 

Summary of Contents for 80CM008J24

Page 1: ...www delta dct com VRF Compact Four Way Cassette Indoor Units 80CM SERIES INSTRUCTION MANUAL WARNING Read and follow all safety precautions in Instruction Manual improper use can cause serious injury...

Page 2: ...allation of the Indoor Unit 7 4 2 Installation of the Connection Pipe 8 4 3 Installation and Test of Drain Pipe 10 4 4 The Panel Installation 13 5 Introduction of DIP Switch 15 5 1 Function DIP Switch...

Page 3: ...the installation manual and the national electrical wiring rules or code of practice Insufficient capacity or incomplete electrical work may cause electrical shock or fire Be sure to use a dedicated...

Page 4: ...sor is not attached and the stop valve is open during pump down air will be sucked in when the compressor is run causing abnormal pressure in the freezer cycle which will lead to breakage and even inj...

Page 5: ...emperature C DBTemperature C WBTemperature C Rated Cooling 27 19 35 24 Rated Heeting 20 15 7 6 2 3 Functions of the Unit Functions of the Wired Controller Mode Setting Lock Temperature Setting Shieldi...

Page 6: ...nit 6 Wireless Controller 1 To control the indoor unit 7 Insulation 1 To insulate the gas pipe 8 Insulation 1 To insulate the liquid pipe 9 Fastener 8 To fasten the sponge 10 Paper Template Lifting bo...

Page 7: ...ng noise and oscillate 4 The horizontally of the installation place should be guaranteed 5 Select the place where easy drain condensated coagulated water and easy connect with outdoor unit 6 Make sure...

Page 8: ...eaker Capacity Min Power Supply Cord V Ph Hz A A mm2 80CM008J24 208 230V 60Hz 0 192 6 1 0 80CM010J24 0 192 6 1 0 FLA Full Load Amps 2 Install the disconnect device with a contact gap of at least 3mm i...

Page 9: ...ce boards should be maintained at no less than 20mm 160 Ceiling Installation stands for main body of the unit Above 20 Fig 3 4 1 2 Installing the Main Body Unit 1 Primary Step for Installing the Indoo...

Page 10: ...vent the gasket from breaking off and tighten the nut on it 5 Backout the reference cardboard Fig 4 4 2 Installation of the Connection Pipe 1 When connecting the pipe to the unit or backout it from th...

Page 11: ...inlet tube Gas collection tube Torque wrench Median sponge attachment entwine the wiring interface with seal mat Thread fasten x4 Smear freeze motoroil here Fig 5 Table 1 Tightening Torques Needed fo...

Page 12: ...ng tape accessory Fig 6 4 3 2 Installing the Drain Pipes 1 Insert the drain hose into the drain socket up to the base and tighten the clamp securely with the tape 2 Insert the drain hose into the drai...

Page 13: ...r trap for each unit 8 Installation of water trap shall consider easy cleaning in the future Joint Joint Indoor unit Indoor unit Fig 9 9 Connection of drainage branch pipe to the standpipe or horizont...

Page 14: ...ing stand Roof Drain hose 1000 1500mm 280mm attachment 300mm Fig 13 2 Make sure the raiser piping is at most 280mm 3 Stand the raiser piping horizontally and make sure it is not further than 300mm fro...

Page 15: ...ners for pouring Fig 16 4 4 The Panel Installation 4 4 1 Precautions When Installing the Panel 1 Improper screwing of the screws may cause the troubles as shown in the figure below Water condensatatio...

Page 16: ...14 3 Wiring of the Decoration Panel Connect the joints for the swing flap motor lead wire at 2 places installed on the panel At body At panel Fig 19...

Page 17: ...under STOP state before power failure it will be also under STOP state after the power supply is resumed DIP switch 2 L I Setting of the control mode through either the wired controller or the remote...

Page 18: ...mainboard of indoor unit If wired controller is used make sure to set the address of wired controller to the position same as the address code on corresponding indoor unit The address of wired contro...

Page 19: ...s shown above is related to the maximum capacity of the indoor unit Capacity Code The capacity code of the capacity DIP switch is in binary format When the switch is set to ON it indicates 1 of the bi...

Page 20: ...oard Supplied 4 core cable CN18 CN1 Fig 21 Power communication Wiring illustration of wired controller When connect wired controller to main board use a 4 cores cable to set up a communication wiring...

Page 21: ...trip all the poles of the wiring and has an isolation distance of at least 3 mm between the contacts of each pole Perform wiring work in accordance with standards so that the air conditioner can be op...

Page 22: ...4 Position the round terminal wire and replace and tighten the terminal screw with a screwdriver A Solid wire B Strand wire 25 10 Insulation Round terminal Fig 22 7 2 2 How to Fix Connection Cord and...

Page 23: ...nit is turned off press TEST button located at the corner of the panel then the unit begins to run under heating mode with high fan speed The temperature will be set to 20 C automatically When the uni...

Page 24: ...n pull them downward slowly 2 Remove the air filters Slide knobs on the back of the suction grille outward and remove the air filter Fig 24 3 Clean the air filter Use vacuum or wash the air filter wit...

Page 25: ...arthed reliably 3 Check if the air filter had been installed well 4 In order to start up the air conditioner smoothly after long time s turned off turn on the main power supply 8 hours before turning...

Page 26: ...e set temperature is too high The heating effect is not good The air filter screen is dirty or is clogged The door or window is not closed fully The set temperature is too low The remote controller is...

Page 27: ...47 47 47 Input of Motor kW 0 05 0 05 0 05 0 05 Power Supply 208 230V phase 60Hz Anti electric Shock Protect Type I Dimensions mm WhDhH Main body h h Panel h h Net Weight kg Main body Panel 20 2 5 The...

Page 28: ...Thank you for Choosing airconditioners Perfectly engineered for your comfort www delta dct com...

Reviews: