TECHNICAL DATASHEET
PMT Panel Mount Power Supply
36V 350W 1 Phase / PMT-36V350W1A
□
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (April 2015, Rev. 01)
9
Assembly & Installation
Ⓐ
Side Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply assembly onto a metal mounting surface. The
power supply shall be mounted on minimum of 4 mounting holes using M4 screw maximum 5mm length (Refer to Fig. 4). This is
to maintain a safety distance between the screw and internal components.
Ⓑ
Base Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply assembly onto a metal mounting surface. The
power supply shall be mounted on minimum of 4 mounting holes using M4 screw maximum 4mm length (Refer to Fig. 4).
Ⓒ
Connector
Ⓓ
This surface belongs to customer’s end system or panel where the power supply is mounted.
Base Mounting (Horizontal)
Base Mounting (Vertical)
Side Mounting (Horizontal)
Fig. 2
Mounting Orientation
– Use flexible cable (stranded or solid) of AWG No. 22-12. The input/output connectors’ allowable current is 23A max per pin. User
should calculate and select the suitable wire specification (type/quantity/diameter) according to actual output current. The torque at
the connector shall not exceed 13Kgf.cm. The insulation stripping length should not exceed 0.275” or 7mm.
– Recommended mounting torque of the product and its mounting accessories is 9~12Kgf.cm.
Fig. 4 Assembly Reference
Only use M4 screw
≤ 5 mm through the base mounting holes at
Ⓐ
.
This is to keep a safe distance between the screw and internal
components.
Only use M4 screw
≤ 4 mm through the base mounting holes at
Ⓑ
.
Fig. 3 Mounting Hole Locations and the Safety Distance
For safety reasons, please ensure the
mounted device is kept at ≥ 4mm safety distance at all sides from other components and
equipments. In addition, to ensure sufficient convection cooling, always maintain a distance of ≥ 20mm from fan ventilated su
rfaces
while the device is in operation. Please insert an insulation sheet between the system and product, if the safety distance is < 4mm.
Safety Distance
D1 = 4mm Min.
D2 = 20mm Min
.