background image

TECHNICAL DATASHEET

 

PMT Panel Mount Power Supply 

36V 350W 1 Phase / PMT-36V350W1A

□ 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  

www.DeltaPSU.com (April 2015, Rev. 01)

  

 

8

 

 

Engineering Data 

De-rating 

 

 

 

 

 

 

 

 

Output De-rating VS. Input Voltage 

 

 

 

 

Note 

 

1.  Power supply components may degrade, or 

be damaged, when the power supply is 

continuously used outside the shaded region, 

refer to the graph shown in Fig. 1.  

2.  If the output capacity is not reduced when the 

surrounding air temperature >50°C, the 

device will run into Over Temperature 

Protection. When activated, the output 

voltage will go into bouncing mode and will 

recover 

when the surrounding air 

temperature is lowered or the load is reduced 

as far as necessary to keep the device in 

working condition.  

3.  In order for the device to function in the 

manner intended, it is also necessary to keep 

a  safety  distance  of  ≥  20mm  with  adjacent 

units while the device is in operation. 

4.  Depending on the surrounding air 

temperature and output load delivered by the 

power supply, the device housing can be 

very hot!  

5.  If the device has to be mounted in any other 

orientation, please do not hesitate to contact 

[email protected]

 for more details. 

Fig. 1  De-rating for Vertical and Horizontal Mounting Orientation 

 

 > 50°C de-rate power by 2.5% / °C 

 

No output power de-rating for the input 

voltage from 100Vac to 132Vac & 200Vac to 

264Vac 
 

  

           

  

 

 

Summary of Contents for 36V350W1AR

Page 1: ...age of 36V with a wide operating temperature range from 10 C to 70 C and can withstand shock and vibration in accordance to IEC 60068 2 27 and IEC 60068 2 6 respectively In addition to features like o...

Page 2: ...A 240Vac Output Ratings Characteristics Nominal Output Voltage 36Vdc Output Voltage Tolerance 1 initial set point tolerance from factory Output Voltage Adjustment Range 32 4 39 6Vdc Output Current 9 7...

Page 3: ...er axis for all X Y Z direction Pollution Degree 2 Protections Overvoltage 41 4V 48 6V Latch Mode Overload Overcurrent 105 150 of rated load current Hiccup Mode Non Latching Auto Recovery Over Tempera...

Page 4: ...ransient Burst IEC 61000 4 4 Level 3 Criteria A1 2kV Surge IEC 61000 4 5 Level 3 Criteria A 1 Common Mode 2 2kV Differential Mode 3 1kV Conducted IEC 61000 4 6 Level 3 Criteria A 1 150kHz 80MHz 10Vrms...

Page 5: ...at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com April 2015 Rev 01 5 Block Diagram Device Description 1 Input Output terminal block connector 2 DC voltage adjustment potentiome...

Page 6: ...Power Supply 36V 350W 1 Phase PMT 36V350W1A All parameters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com April 2015 Rev 01 6 Dimensions L x W x D 215 x 115 x...

Page 7: ...l Mount Power Supply 36V 350W 1 Phase PMT 36V350W1A All parameters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com April 2015 Rev 01 7 L x W x D 215 x 115 x 50 m...

Page 8: ...ltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition 3 In order for the...

Page 9: ...ounting Orientation Use flexible cable stranded or solid of AWG No 22 12 The input output connectors allowable current is 23A max per pin User should calculate and select the suitable wire specificati...

Page 10: ...er supply Do not touch the device while it is in operation or immediately after power is turned OFF Risk of burning Do not touch the terminals while power is being supplied Risk of electric shock Prev...

Page 11: ...a certain period of time The time required for the output to reach 95 of its set value after the input voltage is removed Graph illustrating the Start up Time Rise Time and Hold up Time Inrush Curren...

Page 12: ...U Short Circuit Protection The power supply s output OLP OCP function also provides protection against short circuits When a short circuit is applied the output current will operate in Hiccup mode as...

Page 13: ...ut from DRR module will be VO output voltage of power supply Vdrop in DRR module Parallel Operation These DRR modules can also be used for Parallel function in order to increase the output power by N...

Page 14: ...striction of the usage of hazardous substances The European directive 2011 65 EU limits the maximum impurity level of homogeneous materials such as lead mercury cadmium chrome polybrominated flame ret...