Floor Ceiling Air-Conditioning Unit
16
4.5.2 Additional Charge
Refrigerant suitable for a piping length of 5m is charged in the outdoor unit at the factory.
When the piping is longer than 7 m, additional charging is necessary.
For the additional amount, see Table 9.
Table 9
Item
Model
Additional Refrigerant Amount for Extra Pipe Length
54 g/m
54 g/m
54 g/m
110 g/m
4.6 Installation of the Drain Pipe
4.6.1 Precautions When Doing the Piping Work
(1) Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so
that air may not remain trapped inside the pipe.
(2) Keep pipe size equal to or greater than that of the connecting pipe.
(3) Install the drain piping as shown and take measures against condensation. Improperly
rigged piping could lead to leaks and eventually wet furniture and belongings.
Extension drain piping
(commercially available)
Insulating tube
(commercially
available)
Indoor unit
drain hose
Insulating tape
(accessory)
Fig.19
(4) Connect the drain hose.(Fig.20)
Drain hose must
slope downward.
Allow no trap to
form in the piping
Do not allow end
of hose to touch
water
Fig.20