Floor Ceiling Air-Conditioning Unit
6
Table 4
Outdoor Units
Power Supply
Fuse Capacity
Breaker
Capacity
Min. Power
Supply Cord
V/Ph/Hz
A
A
mm
2
31VA024C24
220/230/1/60
24.83
20
2.10
31VA036C24
220/230/1/60
41.93
40
5.30
31VA048C24
220/230/1/60
51.88
50
8.40
31VA060C24
220/230/1/60
65.83
60
8.40
“*” the fuse is located on the main board.
Notes
:
① .
Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units
(Both indoor unit and outdoor unit).The appliance must be positioned so that the plug is
accessible.
② .
The specifications of the breaker and power cable listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
③ .
The specifications of the power cable listed in the table above are applied to the conduit-
guarded multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and
a PVC cable jacket) used at 40°С and resistible to 90°С(see IEC 60364-5-52). If the working
condition changes, they should be modified according to the related national standard.
④ .
The specifications of the breaker listed in the table above are applied to the breaker with
the working temperature at 40°С. If the working condition changes, they should be modified
according to the related national standard.