DO 9861T humidity and temperature transmitters convert the humi-
dity and temperature measured by two sensors into a 4÷20 mA
signal.
An LCD indicator allows the value of the process signal and the various para-
meters to be displayed.
The accurate design and choice of components make the instruments preci-
se and reliable for a long working life. The R.H. sensor is temperature com-
pensated.
The instruments have two sensors, a capacitive sensor for measuring relative
humidity and a Platinum resistive sensor (Pt100, 100 

at 100°C) for measu-

ring temperature.
The transmitters measure the relative humidity (% RH), the sensor tempera-
ture (TC), and calculate the wet bulb temperature (WT), the dew point tempe-
rature (DP), the absolute humidity (gr/m

3

) and the mixing ratio (gr/kg - grams

of water per kg of dry air). The temperatures are expressed in degrees
Celsius.

The measurements refer to an atmospheric pressure of 1013.25 mbar.
Once the physical quantity to be checked has been selected, the output current
will be proportional and the status of the relays will depend on that variable.

Technical characteristics DO 9861T

Key functions

PRG

Programming of the parameters is activated by pressing the PRG
key along with the 

s

and 

t

keys. The message P1 appears on the

display to indicate that parameter P1 is being programmed. When
the PRG key is pressed in sequence the messages P2, P3, etc.
appear as well as the corresponding parameters. After P13 the
instrument returns to normal function.

SET

Key for setting the relay intervention threshold. The ON or OFF sym-
bol appears on the display to indicate that the instrument is showing
the switching on or the switching off threshold of relay A or relay B.

TD/TW When this key is pressed the dry bulb temperature TD or the wet

bulb temperature TW is shown at the top of the display.

UNIT

- When this key is pressed the dew point temperature (DP), the rela-

tive humidity (% RH), the absolute humidity (gr/m

3

- grams of water

per cubic metre of dry air) or the mixing ratio (gr/kg, grams of water
per kg of dry air) is shown at the bottom of the display.

- When pressed along with the CAL key it activates the humidity

sensor calibration function.

OK

Confirms the programming parameters, or the relay SET values, and
stores them.

CAL

- When pressed along with the UNIT key it activates the humidity

sensor calibration function.

- Key used to confirm the calibration of the humidity sensor.

s

- Key used to increase the value displayed during programming of

the parameters.

- During programming of the relay SET points.
- During calibration.

t

- Key used to decrease the value displayed during programming of

the parameters.

- During programming of the relay SET points.
- During calibration.

Display

Symbol description
TD

indicates that the value shown is the dry bulb temperature in °C.

TW

indicates that the value shown is the wet bulb temperature in °C.

DP

indicates that the value shown is the dew point temperature in °C.

% RH

indicates that the value shown is the relative humidity.

gr/m

3

indicates that the value shown is the absolute humidity (gr per m

3

of air).

gr/kg

indicates that the value shown is the mixing ratio (gr per kg of dry air).

A

indicates that relay A is ON.

B

indicates that relay B is ON.

ON

indicates that the value shown corresponds to the closing thre-
shold of the contacts of relay A or B.

OFF

indicates that the value shown corresponds to the closing thre-
shold of the contacts of relay A or B.

Programming the parameters

It is possible to select the corresponding quantities:
- Dry bulb temperature (TD °C)
- Wet bulb temperature (TW °C)
- Dew point temperature (DP °C)
- Relative humidity (% RH)
- Absolute humidity (a gr/m

3

)

- Mixing ratio (x gr/kg).

The range that may be set for each quantity is:
- Dry bulb, wet bulb and dew point temperature: -60.0...+100.0°C
- Relative humidity: 0.0...100.0% RH
- Absolute humidity: 0.0...1999 gr/m

3

- Mixing ratio: 0.0...1999 gr/kg.

Parameters for the DO 9861T

P1

Physical quantity on which depends the operation of the analog output 1
(TD, TW, DP, % RH, gr/m

3

, gr/kg).

P2

Physical quantity on which depends the operation of the analog output 2
(TD, TW, DP, % RH, gr/m

3

, gr/kg).

P3

Value corresponding to 4 mA at analog output 1.

P4

Value corresponding to 20 mA at analog output 1.

P5

Value corresponding to 4 mA at analog output 2.

P6

Value corresponding to 20 mA at analog output 2.

P7

Physical quantity on which depends the operation of relay A (TD, TW,
DP, % RH, gr/m

3

, gr/kg).

P8

Physical quantity on which depends the operation of relay B (TD, TW,
DP, % RH, gr/m

3

, gr/kg).

P9

Delay time in intervention of relay A. May be set between 0 and 255
seconds both during the opening and the closing.

P10 Delay time in intervention of relay B. May be set between 0 and 255

seconds both during the opening and the closing.

P11 Calibration of Pt100 probe.
P12 Current calibration of output 1 at 4 mA and 20 mA.
P13 Current calibration of output 2 at 4 mA and 20 mA.
P14 R.H. calibration after the replacement of R.H. sensor.
To alter one of the parameters, press the PRG key until the message corre-
sponding to the parameter that is to be changed appears on the display.

Capacity

Transducer energizing

Cable length

Accuracy

Working range of sensor

2/4 wires Pt100

Transducer energizing

Cable length

Accuracy

4.00...20.00 mA

Accuracy

Load resistance

A and B

Passive

Active

Front panel

External dimensions

Protection class

Safety

Electrostatic discharges

Fast electric transient

High energy transient

Voltage variation

Sucseptibility to 

electromagnetic interference

Emission of 

electromagnetic interference

390...570 pF

10 kHz

<10 m multiple screen (about 2 nF)

additional error about 0.003 pF/pF

Instrument: 0.1% of reading ±1 digit ±0.01%/°C

Sensor: ±2.5% (5...90%), +3/-2.5% (90...98%)

Relative humidity: 5...98% @ 23°C

Dew point temperature (DP°C):

-60..+100 DP°C (-20 DP°C @ 23°C)

Temperature range: -40..+150°C

-50...+199.9°C

0.5 mA DC

<10 m not screened

<50 m screened (about 5 nF)

0.2°C ±0.1% of reading ±0.01°C/°C

Dry bulb temperature -50.0...+199.9°C

Wet bulb temperature -50.0...+199.9°C

Relative humidity 0.0...+100.0% RH

Absolute humidity 0.0...+1999 gr/m

3

Mixing ratio 0.0...+1999 gr/Kg of air

±2.5% RH

0.5% of reading ±0.02 mA

R

Lmax

=

Vdc-10

R

Lmax

= 636 

@ Vdc = 24 Vdc

0,022

Bistable exchange contacts 3 A/230 V ac potential 

free contact

4÷20 mA, 10...35 V dc, see figure 2

24 or 230 V ac -15/+10%, 1 VA, 48...62 Hz, see figure 1

122x120 mm

122x120x56 mm

IP64

EN61010-1 level 3

EN61000-4-2 level 3

EN61000-4-4 level 3

EN61000-4-5 level 3

EN61000-4-11

IEC1000-4-3 10 V/m

EN55020 class B

Relative humidity

input

Temperature input

Relay

utputs

Feed

Case

CE

Conformity

During use, check that the sensor is compatible with the atmosphere used

Output current A and B

R

Load

Summary of Contents for DO 9861T

Page 1: ...DO 9861T TRASMETTITORE DI UMIDIT E TEMPERATURA TEMPERATURE AND HUMIDITY TRANSMITTER TRANSMETTEUR D HUMIDITE ET DE TEMPERATURE FEUCHTE UND TEMPERATURTRANSMITTER TRANSMISORE DE HUMEDAD Y TEMPERATURA...

Page 2: ...lo stato ON ON indica che il valore visualizzato corrisponde alla soglia di chiusura dei contatti del rel A o B OFF indica che il valore visualizzato corrisponde alla soglia di apertura dei contatti d...

Page 3: ...i umidit relativa Aspettare almeno 30 minuti Premere il pulsante PROG fino a che sul display compare la scritta P14 Premere contemporaneamente i pulsanti CAL e OK Con i pulsanti se taggiustare il valo...

Page 4: ...8 12 12 16 16 20 24 20 22 22 24 mA mA Valori di default rel B P5 P3 P6 P4 P1 C P2 RH Es P7 C Es P8 RH 56 0 mm 122 mm 120 0 mm 21 0 mm PG7 DIMENSIONI 24 Vac o 230 Vac mA B A 12 11 9 8 7 6 5 4 3 GND 4 2...

Page 5: ...es that relay B is ON ON indicates that the value shown corresponds to the closing thre shold of the contacts of relay A or B OFF indicates that the value shown corresponds to the closing thre shold o...

Page 6: ...3 as per the following instructions Insert the probe in the container of the 75 R H saturated solution Wait at least 30 minutes Press the PROG key until the message P14 appears on the display Press CA...

Page 7: ...air sec Les temp ratures sont exprim es en degr s Celsius Les mesures se r f rent une pression atmosph rique de 1013 25 mbar D s qu on s lectionne la grandeur physique contr ler le courant de sortie...

Page 8: ...r d sir e Appuyer sur la touche OK pour confirmer Avant de commencer la programmation s lectionner la grandeur visualiser l aide des touches TD TW et UNIT l appareil consid re cette valeur comme defau...

Page 9: ...r le display appara t le sigle 4 0 pour indiquer l talonnage 4 mA l aide des touches set tr gler la valeur du courant de sortie de fa on obtenir une indication de 4 00 mA sur le milliamp rem tre de r...

Page 10: ...nach die Schriften P2 P3 usw sowie die entsprechenden Parameter Nach P13 kommt man zum Normalbetrieb zur ck 10 Kapazit t Me frequenz Kabell nge Genauigkeit Arbeitsbereich des Sensors 2 4 Leiter Pt100...

Page 11: ...nnen wird mu mit den Tasten TD TW und UNIT die gew nschte Gr e eingestellt werden das Ger t nimmt diese Gr e als Default Wert Nach Stromausfall wird wiederum dieselbe Gr e angezeigt Um die Me gr e zu...

Page 12: ...Teil 20 0 als Meldung da die 20 mA geeicht werden Mit den Tasten s und t den Ausgangsstrom so ver ndern da das Pr zisionsmilliamperemeter 20 00 mA anzeigt Zur Best tigung Taste OK dr cken Fehlermeldu...

Page 13: ...que el rel B est en ON ON indica que el valor visualizado corresponde al umbral de cierre de los contactos del rel A o B OFF indica que el valor visualizado corresponde al umbral de apertura de los co...

Page 14: ...tecla PROG hasta que aparezca el mensaje P14 en el display Pulsar las teclas CAL y OK a la vez Con las teclas sy tajustar el valor de humedad relativa indicado en el display al valor correcto de la s...

Page 15: ...A RELE OFF RELE OFF 0 0 4 4 8 8 12 12 16 16 20 24 20 22 22 24 mA mA Valores de default rel B P5 P3 P6 P4 P1 C P2 RH Es P7 C Es P8 RH 56 0 mm 122 mm 120 0 mm 21 0 mm PG7 DIMENSIONES CORTO CIRCUITO ENTR...

Page 16: ...ontinuellement nos produits nous r servons le droit de le modifier sans pr avis Wir entwickeln unsere Produkte weiter und behalten uns das Recht der nderung vor Mejoramos continuamente nuestros produc...

Reviews: