33 / 53
5.5
M
EASUREMENT
O
PTIMISATION
P20: - - - a Damping
This parameter can be used to reduce unwanted fluctuation of the display and output.
a
Damping
time
(seconds)
LIQUIDS
None/moderate
fume or waves
Heavy/dense fume or
turbulent waves
0
no filter
1
3
applicable
not recommended
2
6
recommended
applicable
3
10
recommended
recommended
4
30
recommended
recommended
5
60
recommended
recommended
FACTORY DEFAULT: 60 sec
P22: - - - a Dome top tank compensation
This parameter can be used to reduce disturbing effect of possible multiple echos.
a
Compensation
Applied
0
OFF
In case the DMSP400/500 is not mounted in the centre of the top and the top is flat.
1
ON
In case the DMSP400/500 is mounted in the centre of a tank with dome-shaped top
FACTORY DEFAULT: 0
P24: - - - a Target tracking speed
In this parameter evaluation can be speed up at the expense of the accuracy.
a
Tracking speed
Remark
0
Standard
For most applications
1
Fast
For fast changing level
2
Special
Only for special applications (measuring range is reduced to 50% of the nominal value)
The measuring window is inactive and the DMSP400/500 will respond practically instantly to any
target. Recommended to fast target tracking, but usually not applicable for level metering.
FACTORY DEFAULT: 0